Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
BACnet Communications - Thermal Management Products
267
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Customer Input 3 - Event Type 
The event type for the [Customer Input 3] event. 
Customer Input 3 
Customer input 3. 
Customer Input 4 - Event Control 
Enable/disable the activation of the [Customer Input 4] event. If set to 'disabled', 
the event will not be annunciated. This implies that the event will not be placed in 
any active event list or in any event history list. 
Customer Input 4 - Event Type 
The event type for the [Customer Input 4] event. 
Customer Input 4 
Customer input 4. 
Dehumidification Proportional Band 
Humidity control band above [Humidity Set Point]. If measured humidity is within 
this band, dehumidification operations are proportionally controlled. 
Dehumidifier Hours Exceeded 
Operating hours for the dehumidifier have exceeded the threshold. 
Dehumidifier Utilization 
Present dehumidifier utilization expressed as a percentage of the maximum 
rated capacity. 
Dig Scroll Comp 1 Over Temp 
Digital scroll compressor 1 shut off because its head temperature has exceeded 
the upper threshold. 
Dig Scroll Comp 1 Temp Sensor Issue 
Digital scroll compressor 1 temperature sensor is disconnected or the signal is 
out of range. 
Electric Reheater Hours Exceeded 
Operating hours for electric reheater have exceeded the threshold. 
Ext Compressor Lockout - Event Control 
Enable/disable the activation of the [Ext Compressor Lockout] event. If set to 
'disabled', the event will not be annunciated. This implies that the event will not 
be placed in any active event list or in any event history list. 
Ext Compressor Lockout - Event Type 
The event type for the [Ext Compressor Lockout] event. 
Ext Compressor Lockout 
The compressor is shut down and disabled by an external input signal. 
Ext Condenser Pump High Water 
High water is detected in the condenser, as indicated by an external input signal. 
Ext Humidifier Lockout - Event Control 
Enable/disable the activation of the [Ext Humidifier Lockout] event. If set to 
'disabled', the event will not be annunciated. This implies that the event will not 
be placed in any active event list or in any event history list. 
Ext Humidifier Lockout - Event Type 
The event type for the [Ext Humidifier Lockout] event. 
Ext Humidifier Lockout 
The humidifier is shut down and disabled by an external input signal. 
Ext Loss of Flow - Event Control 
Enable/disable the activation of the [Ext Loss of Flow] event. If set to 'disabled', 
the event will not be annunciated. This implies that the event will not be placed in 
any active event list or in any event history list. 
Ext Loss of Flow - Event Type 
The event type for the [Ext Loss of Flow] event. 
Ext Loss of Flow 
Loss of flow is detected, as indicated by an external input signal. 
Ext Over Temperature - Event Control 
Enable/disable the activation of the [Ext Over Temperature] event. If set to 
'disabled', the event will not be annunciated. This implies that the event will not 
be placed in any active event list or in any event history list. 
Ext Over Temperature - Event Type 
The event type for the [Ext Over Temperature] event. 
Ext Over Temperature 
A temperature has exceeded its threshold, as indicated by an external input 
signal. 
Ext Reheat Lockout - Event Control 
Enable/disable the activation of the [Ext Reheat Lockout] event. If set to 
'disabled', the event will not be annunciated. This implies that the event will not 
be placed in any active event list or in any event history list. 
Ext Reheat Lockout - Event Type 
The event type for the [Ext Reheat Lockout] event. 
Ext Reheat Lockout 
The reheater is shut down and disabled by an external input signal. 
Ext Standby Glycol Pump On 
The standby glycol pump is on, as indicated by an external input signal. 
External Fire Detected 
Fire detected, as indicated by an external input signal. 
Fan Control Mode 
Fan control mode. Allowable modes are: (0) Auto - Fan speed is controlled via 
the selected fan control sensor, and, (1) Manual - Fan will operate at a fixed 
speed. 
Fan Control Sensor 
Sensor from which air temperature measurements will be used for fan speed 
control. 
Table 86
Liebert CRV
 - Glossary (continued)
Data Label
Data Description