Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - Thermal Management Products
23
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Remote Sensor Temperature 9
30559
 —
1
10
deg C
2, 3, 4, 5, 6
Remote Sensor Temperature 9
30779
 —
1
10
deg F
2, 3, 4, 5, 6
Remote Sensor Temperature 10
30560
 —
1
10
deg C
2, 3, 4, 5, 6
Remote Sensor Temperature 10
30780
 —
1
10
deg F
2, 3, 4, 5, 6
Air Economizer Availability
30561
 —
1
 —
0 = Not Available
1 = Available
2, 3, 4, 5, 6
Air Economizer Control Source
30562
40562
1
 —
0 = disabled
1 = internal
2 = external
2, 3, 4, 5, 6
Chilled Water Valve Hours
30563
40563
1
 —
hr
2, 3, 4, 5, 6
Cooling Capacity
30564
 —
1
 —
%
2, 3, 4, 5, 6
Cooling Control Temperature
30565
 —
1
10
deg C
2, 3, 4, 5, 6
Cooling Control Temperature
30781
 —
1
10
deg F
2, 3, 4, 5, 6
Fan Speed Control Temperature
30566
 —
1
10
deg C
2, 3, 4, 5, 6
Fan Speed Control Temperature
30782
 —
1
10
deg F
2, 3, 4, 5, 6
Free Cooling Internal Control Mode
30567
40567
1
 —
0 = Disabled
1 = Contact
2 = Temperature
3 = Set Point
2, 3, 4, 5, 6
Humidity Control Sensor
30667
40667
1
 —
0 = Supply
1 = Remote
2 = Return
3, 4, 5, 6
Digital Scroll Compressor Loading 1
30668
 —
1
 —
%
3, 4, 5, 6
Digital Scroll Compressor Loading 2
30669
 —
1
 —
%
3, 4, 5, 6
Static Pressure Set Point
30672
40672
1
10
Pa
3, 6
Unit Static Pressure
30673
 —
1
10
Pa
3, 6
System Static Pressure
30674
 —
1
10
Pa
3, 6
Condenser Low Noise Mode State
30675
 —
1
 —
0 = Inactive
1 = Active (Interval)
2 = Active (Full Day)
3, 4, 5, 6
Condenser Low Noise Mode Schedule 
Control
30676
40676
1
 —
0 = disabled
1 = enabled
3, 4, 5, 6
Condenser Low Noise Mode Max Fan 
Speed
30677
40677
1
 —
%
3, 4, 5, 6
Condenser Normal Mode Max Fan Speed
30678
40678
1
 —
%
3, 4, 5, 6
Condenser Low Noise Mode - Interval Days
30679
40679
1
 —
1 = Monday
2 = Tuesday
4 = Wednesday
8 = Thursday
16 = Friday
32 = Saturday
64 = Sunday
3, 4, 5, 6
Condenser Low Noise Mode - Full Days
30680
40680
1
 —
1 = Monday
2 = Tuesday
4 = Wednesday
8 = Thursday
16 = Friday
32 = Saturday
64 = Sunday
3, 4, 5, 6
Table 8
Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
 - Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale
Notes / Units
Extra
Notes