Modbus 485 and Modbus IP Protocols - Thermal Management Products
25
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Instantaneous Power 1
30860
 —
1
 - 
W
6
Instantaneous Power 2
30861
 —
1
 —
W
6
Instantaneous Power 3
30862
 —
1
 —
W
6
Instantaneous Power 4
30863
 —
1
 —
W
6
Instantaneous Power 5
30864
 —
1
 —
W
6
Instantaneous Power 6
30865
 —
1
 —
W
6
Energy Consumption 1
30870
40870
2
 —
kWH
6
Energy Consumption 2
30872
40872
2
 —
kWH
6
Energy Consumption 3
30874
40874
2
 —
kWH
6
Energy Consumption 4
30876
40876
2
 —
kWH
6
Energy Consumption 5
30878
40878
2
 —
kWH
6
Energy Consumption 6
30880
40880
2
 —
kWH
6
Fluid Input Temperature 1
30900
 —
1
10
deg C
6
Fluid Input Temperature 2
30901
 —
1
10
deg C
6
Fluid Input Temperature 1
30902
 —
1
10
deg F
6
Fluid Input Temperature 2
30903
 —
1
10
deg F
6
Fluid Output Temperature 1
30906
 —
1
10
deg F
6
Fluid Output Temperature 2
30907
 —
1
10
deg F
6
Fluid Flow Rate 1
30908
 —
2
10
l/min
6
Fluid Flow Rate 2
30910
 —
2
10
l/min
6
Unit Cooling Load
31001
 —
2
10
kW
6
Circuit Cooling Load
31003
 —
2
10
kW
6
System Date and Time
39998
49998
2
 —
 —
1, 2, 3, 4, 5, 6
Table 9
Extra notes key to Table 8
Number
Description
1
This point is supported on:
iCOM controller version 1.04.042.STD
2
This point is supported on:
iCOM controller version 2.00.11R for US
iCOM controller version 2.00.12R (for Japan and China – language corrections only)
3
This point is supported on:
iCOM controller version 2.01.23R
4
This point is supported on:
iCOM controller version 2.02.16R
5
This point is supported on:
iCOM controller version 2.03.27.07R
6
This point is supported on:
iCOM controller version 2.01.32.02R
Table 8
Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
 - Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale
Notes / Units
Extra
Notes