Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
BACnet Communications - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
302
MMS Output Apparent Power 
Analog_Value
69
4812_1
RD
Units: kVA 
MMS Output Power 
Analog_Value
70
4811_1
RD
Units: kW 
System Output Apparent Power 
Analog_Value
71
4209_1
RD
Units: kVA 
System Output Power 
Analog_Value
72
4208_1
RD
Units: kW 
Output Current Crest Factor Phs A 
Analog_Value
73
5159_1
RD
Output Current Crest Factor Phs B 
Analog_Value
74
5160_1
RD
Output Current Crest Factor Phs C 
Analog_Value
75
5161_1
RD
System Configuration
System Date and Time
Analog_Value
86
4293_1
RW
Table 100 Liebert APM
, Liebert NXC
, Liebert NXR
 - Multistate Data
Data Label
Object
Type
Instance
Object
Name
Access
Notes
Battery
UPS battery1 status
MultiState_Value
1
4871_1
RD
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
System Status
Inverter On/Off State
MultiState_Value
12
4746_1
RD
1 = off
2 = on
Maintenance Bypass Breaker (MBB)
MultiState_Value
13
4772_1
RD
1 = Open
2 = Close
3 = Not Installed
UPS Output Source
MultiState_Value
14
4872_1
RD
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reduced
System Status
MultiState_Value
15
4123_1
RD
1 = Normal Operation
2 = StartUp
3 = Normal with Warning
4 = Normal with Alarm
5 = Abnormal Operation
ECO Mode Operation State
MultiState_Value
16
5454_1
RD
1 = disabled
2 = enabled
Table 99
Liebert APM
, Liebert NXC
, Liebert NXR
 - Analog Data (continued)
Data Label
Object
Type
Instance
Object
Name
Access
Notes