BACnet Communications - UPS Systems
303
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Table 101 Liebert APM
, Liebert NXC
, Liebert NXR
 - Glossary
Data Label
Data Description
Battery Auto Test In Progress 
Automatic battery test is in progress 
Battery Capacity Low 
Battery capacity is low 
Battery Charging Error 
The battery is not charging properly 
Battery Charging Inhibited 
Battery charging is inhibited due to an external inhibit signal 
Battery Converter Failure 
Battery converter failure. This is a summary event caused by one or more power sub-
modules in a UPS module.
Battery Discharging 
The battery is discharging 
Battery Equalize 
The rectifier output voltage is increased to equalize the battery voltage level. 
Battery Low 
The calculated battery time remaining has reached the low battery threshold 
Battery Not Qualified 
The UPS battery voltage is not qualified. This event will be detected even in the 
absence of battery disconnect or when it is open. 
Battery Over Temperature 
A battery temperature sensor is reporting a value above a threshold 
Battery Temperature for Cabinet 
The battery temperature for a cabinet 
Battery Terminals Reversed 
The measured battery voltage is a negative value due to reverse battery terminal 
connections. 
Battery Time Remaining 
The calculated available time on battery 
Battery Volts for Cabinet 
The voltage between the positive and negative battery terminals of a battery cabinet 
Bypass - Excess Auto Retransfers 
The number of auto retransfers, from bypass to inverter, has exceeded the maximum 
for a specified time interval 
Bypass Input Frequency 
The bypass input frequency 
Bypass Input Voltage RMS A-N 
The bypass input RMS voltage between phase A and Neutral 
Bypass Input Voltage RMS B-N 
The bypass input RMS voltage between phase B and Neutral 
Bypass Input Voltage RMS C-N 
The bypass input RMS voltage between phase C and Neutral 
Bypass Not Available 
A problem associated with the bypass has been detected 
Bypass Static Switch Unavailable 
The static bypass switch is off, and unable to operate 
DC Bus Abnormal 
The system has detected an abnormal DC Bus Voltage. 
DC Bus Current 
The current at the battery input terminals. In charging mode, the current will be a 
positive value. In discharging mode, the current will be a negative value 
ECO Mode Operation State 
This setting is used to enable or disable ECO Mode. 
Equipment Over Temperature 
Equipment over temperature summary event 
Fuse Failure 
A summary event indicating one or more fuse failures 
Inlet Air Temperature 
The temperature of the inlet air 
Internal Communications Failure 
The control has detected a communication failure of a component on the internal 
communication bus 
Inverter Failure 
Inverter failure - inverter output is off 
Inverter On/Off State 
inverter on/off state 
Inverter Overload Phase A 
Inverter is operating with an overload on phase A 
Inverter Overload Phase B 
Inverter is operating with an overload on phase B 
Inverter Overload Phase C 
Inverter is operating with an overload on phase C 
Inverter SCR Open 
The system has detected an open across one or more inverter static switch Silicon 
Controlled Rectifiers. 
Inverter Shutdown - Overload 
The inverter has shutdown due to a sustained overload 
Inverter Static Switch SCR Short 
The system has detected a short across one or more inverter static switch Silicon 
Controlled Rectifiers (SCR) 
LBS Inhibited 
The system has detected that conditions to perform Load Bus Sync are not satisfied 
Load Impact Transfer 
On bypass as result of load impact.