Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
BACnet Communications - UPS Systems
327
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Table 108 Liebert NXL
 - 60Hz, UL version (Model 40) - Multistate Data
Data Label
Object
Type
Instance
Object
Name
Access
Notes
Liebert
NXL Type
Input
Input Qualification Status
MultiState_Value
1
4735_1
RD
1 = Fail
2 = Marginal Low
3 = Normal
4 = Marginal High
SMS, 1+N, 
N+1
Bypass
Static Bypass Switch
MultiState_Value
12
4736_1
RD
1 = off
SMS, 1+N, 
SCC
Bypass Qualification Status
MultiState_Value
13
4737_1
RD
1 = Fail
2 = Marginal Low
3 = Normal
4 = Marginal High
SMS, 1+N, 
SCC
Battery
UPS Battery Status
MultiState_Value
24
4871_1
RD
1 = Unknown 
2 = Normal
3 = Low
4 = Depleted 
SMS, 1+N, 
N+1
DC Bus
DC Bus Qualification Status
MultiState_Value
35
4743_1
RD
1 = Fail
2 = Marginal Low
3 = Normal
4 = Marginal High
SMS, 1+N, 
N+1
Output
Output Qualification Status
MultiState_Value
46
4744_1
RD
1 = Fail
2 = Marginal Low
3 = Normal
4 = Marginal High
SMS, 1+N, 
N+1, SCC
Inverter
Inverter Output Qualification 
Status
MultiState_Value
57
4745_1
RD
1 = Fail
2 = Marginal Low
3 = Normal
4 = Marginal High
SMS, 1+N, 
N+1
Inverter On/Off State
MultiState_Value
58
4746_1
RD
1 = off
2 = on
SMS, 1+N, 
N+1
Rectifier
Rectifier Pulse Count
MultiState_Value
69
4257_1
RD
1 = 6 Pulse 
2 = 12 Pulse
3 = 18 Pulse
4 = 24 Pulse
SMS, 1+N, 
N+1
Rectifier Input Passive Filter
MultiState_Value
70
4258_1
RD
1 = Not Installed
2 = Installed
SMS, 1+N, 
N+1
Rectifier Passive Filter 
Switch
MultiState_Value
71
4301_1
RD
1 = Not Installed
2 = Installed
SMS, 1+N, 
N+1
Rectifier Active Filter
MultiState_Value
72
4302_1
RD
1 = Not Installed
2 = Installed
SMS, 1+N, 
N+1
Rectifier Status
MultiState_Value
73
4748_1
RD
1 = off
2 = on
SMS, 1+N, 
N+1