Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
BACnet Communications - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
328
System
UPS Module Type
MultiState_Value
84
4303_1
RD
1 = Single Module
System
2 = Module (1 + 1)
3 = Module (1 + N)
4 = Module (N + 1)
5 = System Control
Cabinet 
6 = Main Static Switch
SMS, 1+N, 
N+1, SCC
Bypass Input Wire 
Configuration 
MultiState_Value
85
4304_1
RD
1 = Two Wire (single 
phase + return) 
2 = Two Wire (2 phase, 
no neutral) 
3 = Three Wire (2 
phase + neutral) 
4 = Three Wire (3 
phase, no neutral) 
5 = Four Wire (3 
phases + neutral) 
SMS, 1+N, 
SCC
Output Wire Configuration 
MultiState_Value
86
4305_1
RD
1 = Two Wire (single 
phase + return) 
2 = Two Wire (2 phase, 
no neutral) 
3 = Three Wire (2 
phase + neutral) 
4 = Three Wire (3 
phase, no neutral) 
5 = Four Wire (3 
phases + neutral) 
SMS, 1+N, 
N+1, SCC
Static Switch Type 
MultiState_Value
87
4306_1
RD
1 = Not Applicable 
2 = Continuous Duty 
3 = Momentary Duty
SMS, 1+N, 
SCC
Configuration Description 
MultiState_Value
88
4751_1
RD
1 = Single Module 
System 33 
2 = Single Module 
System 34 
3 = Single Module 
System 44 
4 = 1+1 33 
5 = 1+1 34 
6 = 1+1 44 
7 = 1+N 33 
8 = 1+N 34 
9 = 1+N 44 
10 = N+1 33 
11 = N+1 34 
12 = N+1 44 
13 = SCC w/
Continuous Duty SS 33
14 = SCC w/
Continuous Duty SS 44
15 = SCC w/
Momentary Duty SS
16 = Main Static Switch 
SMS, 1+N, 
N+1, SCC
UPS System Output Source 
MultiState_Value
89
4752_1
RD
1 = off
2 = Normal
3 = Bypass
4 = Maintenance 
Bypass
SMS, 1+N, 
SCC
System Input Power Source
MultiState_Value
90
4318_1
RD
1 = None
2 = Utility (mains) 
3 = Generator 
SMS, 1+N, 
N+1, SCC
Table 108 Liebert NXL
 - 60Hz, UL version (Model 40) - Multistate Data (continued)
Data Label
Object
Type
Instance
Object
Name
Access
Notes
Liebert
NXL Type