Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
58
Table 18
Liebert XDC
 - Status and Coil
Controller
Liebert iCOM
®
 v4
Data Description
Status 
Coil 
Number
of Bits
Scale
Notes / Units
Pump 1 Loss of Flow
10001
1
Active on Alarm
Pump 2 Loss of Flow
10002
1
Active on Alarm
Fan Issue
10003
1
Active on Alarm
System Condensation Detected
10004
1
Active on Alarm
Customer Input 1
10005
1
Active on Alarm
Supply Refrigerant Over Temp
10006
1
Active on Alarm
Supply Refrigerant Under Temp
10007
1
Active on Alarm
Supply Refrigerant Temp Sensor Issue
10008
1
Active on Alarm
Ext Air Sensor A Over Temperature
10009
1
Active on Alarm
Ext Air Sensor A Under Temperature
10010
1
Active on Alarm
Ext Air Sensor A Issue
10011
1
Active on Alarm
Ext Air Sensor B Over Temperature
10012
1
Active on Alarm
Ext Air Sensor B Under Temperature
10013
1
Active on Alarm
Ext Air Sensor B Issue
10014
1
Active on Alarm
Ext Dew Point Over Temperature
10015
1
Active on Alarm
Pump Short Cycle
10016
1
Active on Alarm
Compressor 1A High Head Pressure
10017
1
Active on Alarm
Compressor 1B High Head Pressure
10018
1
Active on Alarm
Compressor 2A High Head Pressure
10019
1
Active on Alarm
Compressor 2B High Head Pressure
10020
1
Active on Alarm
Compressor 1A Short Cycle
10021
1
Active on Alarm
Compressor 1B Short Cycle
10022
1
Active on Alarm
Compressor 2A Short Cycle
10023
1
Active on Alarm
Compressor 2B Short Cycle
10024
1
Active on Alarm
Circuit 1 Low Suction Pressure
10025
1
Active on Alarm
Circuit 2 Low Suction Pressure
10026
1
Active on Alarm
Shutdown - Loss Of Power
10027
1
Active on Alarm
Smoke Detected
10028
1
Active on Alarm
Water Under Floor
10029
1
Active on Alarm
Service Required
10030
1
Active on Alarm