4.1.4. 
Map Descriptor Example 1 – IO Read 
This example provides all the required information to read and write to the IO memory area of the PLC. The following Map 
Descriptor creates a task for the driver to read the first 20 Words from the CIO memory area and store them in the Data 
Array DA_CIO. The first word from the PLC will be stored as the first element in the Data Array. Whenever an upstream 
device writes any element in the Data Array, the Driver will write the same value to the PLC at the corresponding address. 
This scheme is known as Write-thru. In this example the Driver can write only one value at a time. 
 
Map_Descriptor_Name, 
Data_Array_Name, 
Data_Array_Offset, 
Function, 
Node_Name 
Address, 
Length, 
Data_Type, 
Command_Name, 
Unit_number 
CMD_CIO, 
DA_CIO, 
0, 
RDBC, 
PLC1, 
0, 
20, 
CIO-WORD, 
MEMORY AREA READ, 
 
Command Name specifies the Main and 
Sub request codes to make a request to 
read this memory from PLC. 
Assigning Direct MRC and SRC 
parameters can replace this parameter. 
See chapter 6 to know valid MRC –SRC 
values to read this CIO memory area.  
This is the logical name 
of the target device 
having the parameters 
defined in section 
“Client Node 
Descriptors”.  
One of the Data 
Arrays declared in 
the Data_Array 
section 
The Data for CIO 
memory area from 
the Node (PLC1) 
will be stored in this 
Data Array.
 
Offset within the Data 
Array at which Driver will 
the store the data for initial 
Address defined under 
“Address” parameter.   
In particular this case data 
for Address 0 will be 
stored at offset 0, for 
Address 1 offset 1 and so 
on.
 
 
Forcing the Driver to issue a 
read request for each 
Scan_Interval . 
In  particular case Driver 
will read this portion of CIO 
memory area for each 
second if Scan_Interval is set 
1s. 
Starting Address 
of the memory 
area to read.  
Specify the number of 
elements (number of Words 
in this case) to read from 
PLC.  
Specifies the type of target 
memory at PLC. 
Also this parameter can be 
replaced with 
Memory_Code parameter. 
See chapter 6 to for memory 
codes read CIO Word area.  
Unit number at PLC