FS-8704-16 Omron FINS Manual 
 
 
 
 
Page 13 of 37 
 
 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldserver.com 
Tel: (408) 262-2299   Fax: (408) 262-9042   Toll_Free: 888-509-1970   email: support@fieldserver.com 
4.1.6. 
Map Descriptor Example 3: Clock Read:  
This Map Descriptor reads the PLC clock and stores the information in a Data Array DA_CLK. For detail on how the 
Driver stores clock information see Appendix B.1. 
Map_Descriptor_Name, 
Data_Array_Name, 
Data_Array_Offset, 
Function, 
Node_Name, 
Length, 
Command_Name, 
Unit_Number 
CMD_CLKr, 
DA_CLKr, 
0, 
RDBC, 
PLC1, 
7, 
CLOCK READ, 
 
4.1.7. 
Map Descriptor Example 4: Clock Write:  
Write-thru is not possible for Clock write.  A dedicated Map Descriptor is required to overwrite the PLC clock.  This 
Map Descriptor overwrites the clock whenever an upstream device updates the DA_CLKw Data Array. See Appendix 
B.1  for details. 
Map_Descriptor_Name, 
Data_Array_Name, 
Data_Array_Offset, 
Function, 
Node_Name, 
Length, 
Command_Name, 
Unit_Number 
CMD_CLKw, 
DA_CLKw, 
0, 
WRBX, 
PLC1, 
7, 
CLOCK WRITE, 
 
Note:  
All elements must be updated in DA_CLKw to set the clock as expected. Whenever any element updates, the 
Driver will write all seven values to the PLC along with the one updated value. If all elements are updated by the 
upstream device in a single operation then the Driver will also set the all elements at the PLC in a single operation.  
 
4.1.8. 
Map Descriptor Example 5: Read CPU Cycle Times:  
This Map Descriptor reads the CPU cycle time at the PLC and stores the data in a Data Array DA_CYCT. Average, 
maximum and minimum cycle times will be stored in three consecutive locations starting with the location indicated by 
the Data_Array_Offset parameter.  See Appendix B.1 
Map_Descriptor_Name, 
Data_Array_Name, 
Data_Array_Offset, 
Function, 
Node_Name, 
Length, 
Command_Name, 
Unit_Number 
CMD_CYCT, 
DA_CYCT, 
0, 
RDBC, 
PLC1, 
3, 
CLOCK READ, 
0s 
 
The Driver stores these values as it gets them from the PLC.  Scaling can provided to determine the unit in which the 
value is stored.  Default is 10 times milliseconds.