UPS (Uninterruptible Power Supply)
S8700 | 8710
 / 
S8500
 / 
S8300
The UPS MO supports the UPS device for each media server. This MO’s maintenance software 
reacts to UPS-generated in-line errors via SNMP traps.
Note:
Note:
This MO provides no periodic or on-demand tests.
UPS Traps to Media Server
on page 89 contains the various 
UPS-generated SNMP traps to the media server.
Table 25: Enterprise-Specific UPS Traps to Server 
SNMP Trap from UPS
Event
ID
Definition of Trap
Trap (1)
#6
(
Alarm string = #1, ACT, UPS, A, 6, MAJ, power failure: 
Shutting down in 6 minutes.
If the Event ID is 6, the UPS battery’s power is in a 
critically low condition, with an estimated 6 minutes of 
remaining holdover.
A warning is written to every logged-in user of the 
server.
When 6 minutes elapse, the server begins shutting 
down.
(For troubleshooting procedures, see Events #
Trap (1)
#7
(
Alarm string = #1, ACT, UPS, A, 7, MAJ, power failure: 
Shutting down in 7 minutes.
The UPS battery’s power is in a critically low condition, 
with an estimated 7 minutes of remaining holdover.
A warning is written to every logged-in user of the 
server.
When 7 minutes elapse, the server begins shutting 
down.
(For troubleshooting procedures, see Events #