Avaya 03-300430 Manuale Utente
Communication Manager Maintenance-Object Repair Procedures
750 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
System technician-demanded tests:
Descriptions and error codes
Descriptions and error codes
S8700 | 8710
Power/Fan lead query test #(1533)
The Power/Fan Query test sends a request for the state of the power/fan lead (AuxSig) to the
TN2312BP IPSI board in the G650 with an A carrier address. If the lead is on, the test fails. If
the lead is off, the test passes.
TN2312BP IPSI board in the G650 with an A carrier address. If the lead is on, the test fails. If
the lead is off, the test passes.
Order of Investigation
Short test
sequence
sequence
Long test
sequence
D/ND
Power/Fan lead query test (1533)
X
X
Nondestructive
Table 258: Test 1533 Power/Fan lead query
Error
code
code
Test
result
result
Description and recommendation
1000
ABRT
This is an internal system error.
1. Repeat the command at one-minute intervals 1 to 3 times.
2000
ABRT
The response to a query was not received in the time allowed.
1. Repeat the command at one-minute intervals 1 to 3 times.
1
FAIL
G650
: In a G650 carrier, this indicates a failure in any of the following MOs:
●
SER-BUS
●
POW-SUP
●
CAB-TEMP
●
PS-RGEN
Use the diagnostic procedures for those MOs to clear the problem.
1 of 3