CAUTION — Do not run wire behind flanges of Header Plate or 
in any location where it might be damaged.  
Millivolt wall thermostats are specially designed for use on self-
generating systems.  They should never be used on line or low 
voltage A.C. circuits.
Interior Wall — The thermostat should be installed on an inside 
wall away from the furnace but in the same room.  
It is important to use wire of a gauge proper for the length of the 
wire:
RECOMMENDED WIRE GAUGES
 
Maximum Length 
Wire Gauge
 
1' to 10' 
18
 
10' to 25' 
16
 
25' to 35' 
14
Proper operation depends on a good pilot flame.  The flame must 
cover the top of the thermopile.  Cleaning of the pilot orifice and 
burner may be required due to spiders.
System Check (Figure 7)
A millivolt meter is required to check the system.  Millivolt readings 
should be:
•  Across  the  thermopile  terminals,  400-450  millivolts  with  
thermostat OFF.
•  Across  the  thermopile  terminals,  150-250  millivolts  with  
thermostat ON.
•  Across the thermostat wires at the valve, less than 30 millivolts 
with  thermostat ON.
•  Across the thermostat wires at the thermostat, less than 5 millivolts 
with thermostat ON.  (Dirty pilot or low pressure will reduce 
readings.)
Connect thermostat wires to gas valve as shown in Figure 7.
Figure 7
THERMOSTAT LOCATION (SG MODELS)