Empire Products DVC-35T-1 Manuale Utente

Pagina di 24
Page 8
 
13119-6-0107
Figure 3
Checking Manifold Pressure
Both  Propane  and  Natural  gas  valves  have  a  built-in  pressure 
regulator in the gas valve. Natural gas models will have a manifold 
pressure of approximately 4.0” w.c. (.996kPa) for DVC-35T and 
3.5” w.c.  (.871kPa) for DVC-35IPT at the valve outlet with the 
inlet pressure to the valve from a minimum of 5.0” w.c. (1.245kPa) 
for the purpose of input adjustment to a maximum of 7.0” w.c.  
(1.743kPa). Propane gas models will have a manifold pressure 
approximately 10.0” w.c. (2.49kPa) at the valve outlet with the inlet 
pressure to the valve from a minimum of 11.0” w.c. (2.739kPa) 
for the purpose of input adjustment to a maximum of 13.0” w.c. 
(3.237kPa). 
A 1/8” N.P.T. plugged tapping, accessible for test gauge connection, 
is located on the outlet side of the gas control.
The built-in regulator comes on at approximately 1/4th pressure 
and full on in 10 seconds.
Clearances
  1.  In selecting a location for installation, it is necessary to provide 
adequate  accessibility  clearances  for  servicing  and  proper 
installation. A front clearance of 36” is recommended. Do not 
block outlet or inlet air openings on the front grill.
  2.  The DV4T-59-1, 5” to 9” wall depth is the standard vent kit 
provided with the DVC-35T or DVC-35IPT. See Accessories 
Page 6 to order vent kits for wall depths of 8” to 12” or 12” 
to 19”. The use of tubes not supplied by the manufacturer 
results in unsatisfactory performance.
  3.  The DVC-35T and DVC-35IPT can be attached to the wall or 
recessed into the wall up to 9 1/2” in depth but the minimum 
5”    vent/air  intake  system  wall  depth  must  be  maintained. 
Example: If furnace is recessed into the wall at a depth of 
9 1/2”, the minimum wall depth behind the furnace must be 
5”.
  4.  The wall in which the furnace is recessed has (0) zero clearance 
to the furnace sides and top. 
  5.  When using side discharge registers, SOR-1 or SOK-1, the 
furnace cannot be recessed into the wall. 
  6.  Clearance to sidewall or combustible material is 4”.
  7.  Ceiling clearance is 4”.
  8.  Floor and rear wall clearance is (0) zero inches.
  9.  Clearance of 18” is required to sidewall or combustible material 
when flush mounted SOR-1, side outlet register is used.
 10.  The minimum distance from the center of the vent cap to the 
nearest outside corner or obstruction is 12”.
Figure 4
The vent terminal of this direct vent appliance shall be located at 
least 9” from any opening through which flue gases could enter a 
building. The bottom of the vent terminal and the air intake shall 
be located at least 12”  above grade. See vent location, Figure 4.
WARNING: The nearest point of the vent cap should be 
a  minimum  horizontal  distant  of  six  (6)  feet  from  any 
pressure regulator. In case of regulator malfunction, the 
six (6) feet distance will reduce the chance of gas entering 
the vent cap.
CLEARANCES