REQUIREMENTS FOR MASSACHUSETTS
For all side wall horizontally vented gas fueled equipment 
installed  in  every  dwelling,  building  or  structure  used  in 
whole  or  in  part  for  residential  purposes,  including  those 
owned  or  operated  by  the  Commonwealth  and  where  the 
side wall exhaust vent termination is less than seven (7) feet 
above finished grade in the area of the venting, including but 
not limited to decks and porches, the following requirements 
shall be satisfied:
1.  INSTALLATION OF CARBON MONOXIDE DETEC-
TORS. At the time of installation of the side wall horizontal 
vented gas fueled equipment, the installing plumber or 
gasfitter shall observe that a hard wired carbon monoxide 
detector with an alarm and battery back-up is installed on 
the floor level where the gas equipment is to be installed. 
In addition, the installing plumber or gasfitter shall observe 
that a battery operated or hard wired carbon monoxide 
detector with an alarm is installed on each additional 
level  of  the  dwelling,  building  or  structure  served  by 
the side wall horizontal vented gas fueled equipment. It 
shall be the responsibility of the property owner to secure 
the services of qualified licensed professionals for the 
installation of hard wired carbon monoxide detectors
 
a.  In the event that the side wall horizontally vented gas 
fueled equipment is installed in a crawl space or an 
attic, the hard wired carbon monoxide detector with 
alarm and battery back-up may be installed on the 
next adjacent floor level.
 
b.  In the event that the requirements of this subdivision 
can not be met at the time of completion of installa-
tion, the owner shall have a period of thirty (30) days 
to comply with the above requirements; provided, 
however, that during said thirty (30) day period, a 
battery operated carbon monoxide detector with an 
alarm shall be installed.
2.  APPROVED  CARBON  MONOXIDE  DETECTORS. 
Each carbon monoxide detector as required in accordance 
with the above provisions shall comply with NFPA 720 
and be ANSI/UL 2034 listed and IAS certified. 
3.  SIGNAGE. A metal or plastic identification plate shall be 
permanently mounted to the exterior of the building at a 
minimum height of eight (8) feet above grade directly in 
line with the exhaust vent terminal for the horizontally 
vented gas fueled heating appliance or equipment. The 
sign shall read, in print size no less than one-half (1/2) 
inch in size, “GAS VENT DIRECTLY BELOW. KEEP 
CLEAR OF ALL OBSTRUCTIONS”.
4.  INSPECTION. The state or local gas inspector of the 
side wall horizontally vented gas fueled equipment shall 
not approve the installation unless, upon inspection, the 
inspector observes carbon monoxide detectors and signage 
installed in accordance with the provisions of 248 CMR 
5.08(2)(a) 1 through 4.
 
(b)  EXEMPTIONS: The following equipment is exempt 
from 248 CMR 5.08(2)(a)1 through 4: 
 
 
1.  The  equipment  listed  in  Chapter  10  entitled 
“Equipment Not Required To Be Vented” in the 
most current edition of NFPA 54 as adopted by 
the Board; and 
 
 
2.  Product Approved side wall horizontally vented 
gas  fueled  equipment  installed  in  a  room  or 
structure separate from the dwelling, building or 
structure used in whole or in part for residential 
purposes. 
 
(c)  MANUFACTURER  REQUIREMENTS  -  GAS 
EQUIPMENT VENTING SYSTEM PROVIDED. 
When the manufacturer of Product Approved side 
wall horizontally vented gas equipment provides a 
venting system design or venting system components 
with the equipment, the instructions provided by the 
manufacturer for installation of the equipment and 
the venting system shall include:
 
 
1.  Detailed instructions for the installation of the 
venting  system  design  or  the  venting  system 
components; and
 
 
2.  A complete parts list for the venting system design 
or venting system. 
 
(e)  A copy of all installation instructions for all Product 
Approved side wall horizontally vented gas fueled 
equipment, all venting instructions, all parts lists for 
venting instructions, and/or all venting design instruc-
tions shall remain with the appliance or equipment 
at the completion of the installation.