Model 
GWT-25 
GWT-35
Input BTU/HR (KW/H) 
25,000 (7.3) 
35,000 (10.3)
Height 
66 1/8" (1679mm) 
66 1/8" (1679mm) 
Width 
16" (406mm) 
16" (406mm)
Depth 
6" (152mm) 
6" (152mm)
Gas Inlet Pipe 
1/2"  
1/2" 
Vent Pipe Type B Oval 
4" (102mm) 
4" (102mm)
Accesorios 
Blower Kit 
GWTB-2 
GWTB-2
Rear Register Kit 
GWTR-1 
GWTR-1
Out-of-the-Wall Kit 
GWTW-2 
GWTW-2
Attention: When the GWTW-2, Out-of-the-Wall kit is used the GWTR-1, Rear Register kit cannot be used.
SPECIFICATIONS
Introduction
Vented wall furnace is shipped ready to install in a 2" x 4"  stud 
wall, with studs 16" (406mm) center to center.  Always consult 
your  local  Building  Department  regarding  regulations,  codes 
or ordinances which apply to the installation of a  vented wall 
furnace.
Instructions to Installer
1.  Installer  must  leave  instruction  manual  with  owner  after 
installation.
2.  Installer must have owner fill out and mail warranty card 
supplied with furnace.
3.  Installer should show owner how to start and operate furnace 
and thermostat.
Warning:
Any change to this furnace or its control can be dangerous.  
This is a heating appliance and any panel, door or guard 
removed for servicing an appliance must be replaced prior 
to operating the appliance.
General Information
This series is design certified in accordance with American National 
Standard / CSA Standard Z21.86 and CSA 2.32 by the Canadian 
Standards Association, as a Vented Wall Furnace and must be 
installed according to these instructions.
Any  alteration  of  the  original  design,  installed  other  than 
as shown in these instructions or use with a type of gas not 
shown on the rating plate is the responsibility of the person 
and company making the change.
Important
All correspondence should refer to complete Model No., Serial 
No. and type of gas.
Notice:  During initial firing of this furnace, its paint will bake 
out and smoke will occur.  To prevent triggering of smoke alarms, 
ventilate the room in which the furnace is installed.
Installation in Residential Garages
Gas utilization equipment in residential garages shall be installed 
so that all burners and burner ignition devices are located not less 
than 18" (457mm) above the floor.
Such equipment shall be located, or protected, so it is not subject 
to physical damage by a moving vehicle.  
Qualified Installing Agency
Installation and replacement of gas piping, gas utilization equipment 
or  accessories  and  repair  and  servicing  of  equipment  shall  be 
performed  only  by  a    qualified  agency.    The  term  "qualified 
agency"  means  any  individual,  firm,  corporation  or  company 
which either in person or through a representative is engaged in 
and is responsible for (a) the installation or replacement of gas 
piping or (b) the connection, installation, repair or servicing of 
equipment, who is experienced in such work, familiar with all 
precautions required and has complied with all the requirements 
of the authority having jurisdiction.
State of Massachusetts: The installation must be made by 
a  licensed  plumber  or  gas  fitter  in  the  Commonwealth  of 
Massachusetts.
The installation must conform to local codes  or, in  the absence of 
local codes, with the  National Fuel Gas Code ANSI  Z223.1/NFPA 
54* Natural Gas and Propane Installation Code, CSA B149.1.
*Available from the American National Standards Institute, Inc., 11 West 42nd 
St., New York, N.Y. 10036.
High Altitudes
For altitudes/elevations above 2,000 feet (610m), input ratings 
should be reduced at the rate of 4 percent for each 1,000 (305m) 
feet above sea level. Canadian High Altitudes for locations having 
an elevation above mean sea level between 2,000 feet (610m) and 
4,500 feet (1370m), the manifold pressure is to be decreased from 
3.5" w.c. (.871kPa) to 3.0" w.c. (.747kPa) for Natural Gas and from 
10.0" w.c. (2.49kPa) to 8.0" w.c. (1.992kPa) for Propane Gas.
INTRODUCTION