Empire Products DV-25T-1 Manuale Utente

Pagina di 20
13117-9-0907
Page 8
1.  In selecting a location for installation, it is necessary to provide 
adequate  accessibility  clearances  for  servicing  and  proper 
installation.
2.  Unit is supported by a wall bracket secured to the wall.
3.  The minimum clearances from casing to combustible construction 
is 48" (121cm) on top, 6" (152mm) on each side and 4" (102mm) 
from the floor or from the top surface of carpeting, tile or other 
floor covering and 0" (0mm) to rear wall.
4.  The minimum distance from the center of the vent cap to the 
nearest outside corner or obstruction is 24" (610mm).
5.  The DV-25 and DV-35 minimum wall depth is 4 1/2" (114mm) 
(and the maximum is 13" (330mm).  The use of tubes not 
supplied  by  the  manufacturer  results  in  unsatisfactory 
performance.
The  vent  terminal  of  a  direct  vent  appliance,  with  an  input  of 
50,000 (14.6 KW) BTU per hour or less shall be located at least 9" 
(229mm) from any opening through which flue gases could enter a 
building.  The bottom of the vent terminal and the air intake shall 
be located at least 12" (305mm) above grade.
WARNING:  The nearest point of the vent cap should be 
a minimum horizontal distant of six (6) (1.83m) feet from 
any pressure regulator.  In case of regulator malfunction, 
the six (6) (1.83m) feet distance will reduce the chance of 
gas entering the vent cap. 
Location of Furnace
Pick a location on an outside wall with a clear space of 28" (711mm) 
high by 49" (124cm) wide in the room.
Locating Wall Opening
The furnace is to be located on an outside wall.  Locate wall studs 
so that wall opening will be located between wall studs.  The wall 
studs can be used for attachment of wall mounting bracket.  The 
wall opening required as shown in Figure 3 is a diameter of 7 1/2 
inches (191mm).
A template is provided in furnace carton for positioning furnace 
on the wall.  Also, refer to Figure 3 for positioning the furnace on 
wall and for locating gas line connection.
Figure 4 will position the furnace four inches off the floor.  If it is 
desired to position the furnace higher on the wall, add the difference 
to the "A," "B" and "C" dimensions.  Note: The vent opening is 
not in the center of the furnace.
Figure 3
Figure 4
CLEARANCES
INSTALLATION INSTRUCTIONS