ELECTRICAL INSTALLATION
WARNING: To assure safe operation, installa-
tion must be done by a certified electrician and 
must adhere to local, state and national electrical 
codes.
Use a certified ground fault protection device for 
wet environment installations.
1. Supply voltage must correspond to the voltage 
indicated on unit’s rating plate.
2. The cord from each terminal box must be hard 
wired and properly grounded.
WARNING: Each power supply circuit must be 
provided with a means of disconnection, and the 
disconnecting means must be grouped.
WALL-MOUNTED INSTALLATION
WARNING: Observe minimum clearances shown 
in chart above.
1. Securely fasten the L-shaped brackets to the 
mounting surface using both of the fixing holes in 
the short part of the bracket. NOTE: Wall bolts are 
not supplied: select an appropriate size to provide 
adequate support for the weight of the unit and 
taking into consideration any wind load conditions.
CAUTION: If there is any question about security 
of bolts and fixings, contact a professional con-
tractor.
2. Mount the heater to the brackets with the terminal 
box at the bottom of the heater.
3. Adjust the heater to the desired directional angle, 
then fix in this position by tightening the fixing 
bolts on the brackets at the rear of the heater.
CAUTION: Do not position the heater at an angle 
greater than 50° or less than 30°.
INTRODUCTION
Heat Controller’s infrared heater produces radiant heat that warms people and objects 
rather than the air surrounding them. The heater can be mounted on a wall or ceiling, 
and adjustable brackets allow the heat to be directed where desired. 
This heater is designed for outdoor commercial use only.
MINIMUM CLEARANCE DISTANCES FROM...
MODEL
FLOOR
CEILING
ADJACENT 
WALLS
IR30S
8' (2.44 m)
1' 8" (.51 m)
36" (.91 m)
IR60S
10' (3.05 m) 1' 8" (.51 m) 48" (1.22 m)
Installation & Operation 
Radiant Infrared Heater 
Heat Controller
4. Secure the electrical supply cable so it does not 
come in contact with the heater body or obstruct the 
air vents. Follow local and national electrical code 
requirements.
 CEILING-MOUNTED INSTALLATION
WARNING: Observe minimum clearances shown 
in chart at left.
1. Heater should be hung using non-flexible mount-
ing brackets (not supplied). Select brackets that 
will maintain a minimum clearance of 1' 8" (.51 m) 
from the ceiling.
2. Bolts and fixings (not supplied) should be of an ap-
propriate size to provide adequate support for the 
weight of the unit and any additional load resulting 
from wind conditions.
CAUTION: If there is any question about security 
of bolts and fixings, contact a professional con-
tractor.
3. Secure the heater to the mounting brackets with 
the heater facing directly down.
4. Secure the electrical supply cable so it does not 
come in contact with the heater body or obstruct 
the air vents. Follow local NEC code require-
ments.
ADJUSTING DIRECTIONAL POSITIONING
WARNING! Never attempt to move heater while it 
is operating. Personal injury could result.
1.  Power to the heater from the main supply must be 
OFF to adjust the position. (Turn off circuit breaker.)
2.  Allow the heater to cool before re-positioning the 
angle.
3.  Loosen the fixing bolts on the brackets at the rear 
of the heater; re-position heater as desired, then 
re-tighten the fixing bolts.
CAUTION: Do not position the heater at an angle 
greater than 50° or less than 30°.
3