Figure 16 show a correct pilot flame pattern. The correct flame 
will be blue and will extend beyond the thermocouple. The flame 
will surround the thermocouple just below the tip. A slight yellow 
flame  may  occur  where  the  pilot  flame  and  main  burner  flame 
meet. Figure 17 show an incorrect pilot flame pattern. The incorrect 
pilot flame is not touching the thermocouple. This will cause the 
thermocouple to cool. When the thermocouple cools, the heater 
will shut down.
Correct pilot flame pattern
Figure 16
 Incorrect pilot flame pattern
Figure 17
If pilot flame pattern is incorrect, as shown in Figure 17
•  See Troubleshooting, page 24.
Cleaning and pilot Maintenance
oxygen Depletion Sensor Pilot (Figure 18)
When the pilot has a large yellow tip flame, clean the Oxygen 
Depletion Sensor as follows:
1.  Clean the ODS pilot by loosening nut B from the pilot tubing. 
When this procedure is required, grasp nut A with an open end 
wrench.
2.  Blow air pressure through the holes indicated by the arrows. 
This will blow out foreign materials such as dust, lint and 
spider webs. Tighten nut B also by grasping nut A. 
Figure 18
Warning: 
Never use needles, wires, or similar cylindrical objects to 
clean the pilot to avoid damaging the calibrated ruby that 
controls the gas flow.
pILOT fLAME ChARACTERISTICS
THERMOPILE
PILOT
THERMOCOUPLE
(LPG)
THERMOCOUPLE
(NATURAL)
THERMOPILE
PILOT
THERMOCOUPLE
(LPG)
THERMOCOUPLE
(NATURAL)
A
B