VenTIng InsTallaTIon
Continued
Figure 9 - Typical Offset Installation
Return 
Elbow
Offset 
Elbow
Return 
Elbow
Offset 
Elbow
6' Max.
6' Max.
6' Max.
6' Max.
6' Max.
6' Max.
Return 
Elbow
Offset 
Elbow
Offset 
Elbow
Return 
Elbow
A
B
C
Offset 
Elbow
Ceiling 
Support Pipe 
12S-8DM
Return 
Elbow
ASSEMBLY AND INSTALLATION OF 
DOUBLE WALL CHIMNEY SYSTEM
Each double wall chimney section consists of 
a galvanized outer pipe, a stainless steel in-
ner flue pipe and a wire spacer. Pipe sections 
must be assembled independently as chimney 
is installed. When connecting chimney directly 
to fireplace, inner flue pipe section must be 
installed first with lanced side up. Outer pipe 
section can then be installed over flue pipe 
section  with  hemmed  end  up.  Press  down 
on  each  pipe  section  until  lances  securely 
engage  hem  on  fireplace  starter.  The  wire 
will assure proper spacing between inner and 
outer pipe sections.
Note: For Canada, use chimney parts desig-
nated HT.
  Opening  in  collar  around 
chimney at top of fireplace must 
not  be  obstructed.  Never  use 
blown insulation to fill chimney 
enclosure.
Continue  to  assemble  chimney  sections  as 
outlined,  making  sure  that  both  inner  and 
outer pipe sections are locked together. When 
installing double wall snap-lock chimney to-
gether, it is important to assure joint between 
chimney sections is locked. Check by pulling 
chimney upward after locking. Chimney will 
not  come  apart  if  properly  locked.  It  is  not 
necessary to add screws to keep chimney to-
gether (exception - see Figure 11, page 9).
USING ELBOW OFFSETS (30E-8DM)
1.  To achieve desired offset, you may install 
combinations of 12", 18", 24", 36" and 48" 
length of double wall pipe (see offset chart 
and Figure 9).
 
Note: For systems with 2 elbow sets, mini-
mum height is 22 feet. Maximum height 
for any system is 50 feet.
2.  Chimney  weight  above  offset  rests  on 
return  elbow.  Straps  must  be  securely 
nailed to rafters or joists (see Figure 10, 
details A and B on page 9).
3.  Maximum length of pipe between supports 
(return elbow or 12S-8DM) is 6' of angle 
run. Maximum of two 6' angle run sections 
per chimney system (see Figure 9).
4.  All pipe connections between offset and 
return must be secured with two screws 
on outer pipe only (see Figure 11, page 
9). Do not penetrate inner stainless.