EMI WLH12-S1H2000_101 Manuale Utente
Rome, New York, USA
Enviromaster International LLC
1
emi
eNG
iN
ee
R
iNG Submit
tal
JOB NAME: _____________________________________ LOCATION: _______________________________________
PURCHASER: _____________________________________________________________________________________
ENGINEER: _______________________________________________________________________________________
SUBMITTED TO: _________________________________ FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ]
SUBMITTED BY: _________________________________ DATE:____________________________________________
UNIT DESIGNATION: SCHEDULE #: _______________ MODEL #: ________________________________________
WlH12-S1H2000_101
Single-Zone Cooling / Heat Pump
Rev. A [05/08]
WLH12 ELECTRICAL SPECIFICATIONS
V
olts/
HZ/PH
Fan RLA
Heater
K.W
.
Amps
T
otal
Amps
Min. V
olt
M.C.A.
HACR
BRKR
115/60/1
0.64
–
–
0.64
104
0.8
15
115/60/1
0.64
.75
6.5
7.14
104
8.9
15
208/230/60/1
0.34
–
–
0.34
197
0.4
15
208/230/60/1
0.34
3
13.04
13.38
197
16.7
20
HEAT PUMPS SYSTEM OPTIONS WITH WLH12/S1H2
Cooling
Btuh
Heating
Btuh
SEER HSPF
SHR
EER
COP
11,400
10,600
13.0
8.0
.73
11.5
3.4
WLH
S1H
CapaCities:
Cooling .................... 11,400 Btuh
Heating (High) ........ 10,600 Btuh
Heating (Low)........... 6,200
Heating (High) ........ 10,600 Btuh
Heating (Low)........... 6,200
Btuh
indoor Design temp °F DB/WB
Cooling .............................. 80/67
Heating.............................. 70/57
Cooling .............................. 80/67
Heating.............................. 70/57
Outdoor Design temp °F DB/WB
Cooling .................................95/75
Heating (High) ......................47/43
Heating (Low).......................17/15
Cooling .................................95/75
Heating (High) ......................47/43
Heating (Low).......................17/15
S1H ELECTRICAL SPECIFICATIONS
Model
Volts/HZ/PH
Total
Amps
Min
Volt
M.C.A.
HACR
BRKR
BRKR
S1H2A
115/60/1
10
104
12.2
20
S1H2D
208/230/60/1
5.1
197
6.2
15
stanDarD Features:
evaporator – High Wall mounted:
• Universal unit mounted, infrared compatible control
package, configurable to either unit mount or optional
wall thermostat operation.
• Compatible with most standard wall mounted, 24V
thermostats
• Motorized supply louver
• Integral field condensate pump connector
• Condensate pan over flow protection
• Anti-short cycle compressor protection
• Indoor coil freeze protection
• Dry mode for humidity control (optional electric heat
required)
• Memory back up for auto re-start following power
outage
• Fan purge
stanDarD Features:
Condenser – Side Discharge / vertically arranged:
• R-22 refrigerant
• Factory installed Low Ambient cooling to 32°F
• Duratec compressor protection package
- Suction Accumulator
- Filter dryer
- High pressure switch (manual reset)
- Thermostatically controlled crankcase heater
- Start assist
• Coated wire coils and fan guards
• Five year compressor / one year parts warranty
Thermostatically controlled crankcase heater – This feature
energizes the crankcase heater only when needed, removes
the heater from the electrical circuit at conditions where
it’s not required, saving unnecessary Watts, and increasing
energizes the crankcase heater only when needed, removes
the heater from the electrical circuit at conditions where
it’s not required, saving unnecessary Watts, and increasing
overall system efficiency.