ELECTRICAL REQUIREMENTS
Wire Size
Unit
MUST
Sample Nameplate
120524
COOLING EQUIPMENT
FOLLOWING ITEMS
OUTDOOR GRILLE
INDOOR GRILLE
SAMP
LE
Electrical Rating Tables
4
1
A
5
1
2
1
A
0
2
0
1
A
0
3
All  units  must  be  hard  wired  with  properly  sized  breaker.  See  nameplate  for  specific  chassis  electrical requirements.  
Supply voltage
See Electrical Rating Table below for wire size. Use HACR type breakers to avoid nuisance trips.  All field wiring must be done
in accordance with NEC and local codes.
ELECTRIC SHOCK HAZARD 
WARNING
Turn off electric power before service or instal-
lation.  All  electrical  connnections  and  wiring 
MUST be installed by a qualified electrician and 
conform to the National Electrical Code and all 
local codes which have jurisdiction. Failure to 
do so can result in personal injury and/or death.
Supply voltage to the unit should be a nominal 208/230 volts. It must be between 197 volts and 253 volts. Supply voltage to 
the unit should be checked WITH THE UNIT IN OPERATION. Voltage readings outside the specified range can be expected 
to cause operating problems. Their cause MUST be investigated and corrected.
“Use 
ONLY time delayed fused disconnect or HACR type circuit breaker as indicated on the unit’s rating plate (see 
sample on this page). Proper current protection to the unit is the responsibility of the owner”.