ReMOTe TheRMOsTAT AND LOw VOLTAge CONTROL 
CONNeCTIONs
Remote Thermostat
To control the unit with a wall-mounted thermostat:
  1)  Pull the disconnect switch.
  2)  Unscrew and remove the control box panel.
  3)  After selecting which side you want to run your thermostat
    wire through, run the wires through the side hole in the box
    to reach the connection terminal for the wiring.
  4)  Make the wire connections, appropriately matching the 
    wires as shown in the wiring diagram.
  5)  Once each wire is matched and connected, the unit is now
    controlled by the thermostat.
  6)  Reattach the control box cover.
RT5 (Two speed fan)
RT4 (One speed fan)
Cool   Off   Heat
Auto     On 
All Friedrich Vert-I-Pak units are factory configured to be 
controlled by using a 24V single stage remote wall mounted 
thermostat. The thermostat may be auto or manual changeover 
as long as the control configuration matches that of the 
Vert-I-Pak unit. 
NOTE: An improperly operating, or poorly located room 
thermostat can be the source of perceived equipment 
problems. A careful check of the thermostat and wiring 
must be made then to insure that it is not the source of 
problems. 
Manual Changeover Thermostat
For Heat Pump equipped units: a single stage, heat/cool 
thermostat with a terminal for a reversing valve operation is 
required. Terminal “B” should be continuously energized in the 
heat mode and terminal “G” should be energized whenever 
there is a call for heating or cooling. (Typically, a single stage, 
heat/cool thermostat designed for use with electric heat 
systems will meet the above requirements).
Location
The thermostat should not be mounted where it may be 
affected  by drafts, discharge air from registers (hot or cold), 
or heat radiated from the sun or appliances.
The thermostat should be located about 5 Ft. above the 
fl oor  in  an  area  of  average  temperature,  with  good  air 
circulation. Close proximity to the return air grille is the 
best choice.
Mercury bulb type thermostats MUST be level to control 
temperature accurately to the desired set-point. Electronic 
digital type thermostats SHOULD be level for aesthetics.
 
Thermostat Location
NOTICE
 
DO NOT use a two (2) stage Heat Pump Thermostat.  
Use of this type of thermostat may result in equipment 
and/or property damage