Raypak 182-400 Dépliant

Pagina di 2
Catalog No.:  2000.205D 
Effective:  1-1-08 
Replaces:  4-1-05
 
Raytherm - Type H 
 
 
Hydronic Heating Boilers - Indoor 
Model 
           
 
 
 
       
K
(C)
INDOOR
DRAFT
38"
13-1/4"
GAS
CONNECTION
26-1/2"
10-1/4
3-7/8
3-7/8
26-1/2"
40"
21-1/4"
ELECT.
CONN
STACKLESS
OUTDOOR TOP
PUMP
(OPTIONAL)
PUMP COVER
(OPTIONAL)
J
3/4 NPT
GAS CONNECTION
(OUTDOOR
MODELS ONLY)
11"
 
 
 
 
 
 
 
 
 
Dimensions (Inches) 
Shipping Weight  
(Lbs.) – Approx. 
Model 
No. 
MBTU 
Input 
MBTU 
Output 
AFUE* 
 (%) 
Width 
Height 
 
Flue Dia. 
No Pump  w/ Pump
H-182 181  148  82.6 18-1/4 
62-5/8 12-1/16 
191 
221 
H-260 264  216  82.7 22-3/8 
62-7/8 11-1/8 
214 
244 
H-330 
334 274 N/A 
25-3/4 
63-3/4 10-3/4 
234 
264 
H-400 
399 327 N/A 
29-1/4 
65-3/8 12-1/2 
253 
283 
* With Vent Damper 
NOTE:  Ratings shown are for elevations up to 2,000 feet. For elevations over 2,000, reduce ratings at the rate of 4% for each 
1,000 feet above sea level. 
 
 
 
 
BOILER RATE OF FLOW AND PRESSURE DROP 
10° 
T 
20° 
T 
30° 
T 
Model 
No. 
GPM 
P FT 
GPM 
P FT 
GPM 
P FT
H-182  30  4.2  N/A N/A N/A N/A 
H-260 43 8.5 22 2.2 N/A N/A 
H-330 N/A N/A  27  3.4  N/A N/A 
H-400 
N/A N/A 33 5.2 22 2.3 
N/A – Not Applicable 
 
 
 
Raypak, Inc.  
ƒ  2151 Eastman Avenue, Oxnard, CA  93030  ƒ  (805) 278-5300  ƒ  Fax (800) 872-9725  ƒ  www.raypak.com