Menu: The left Operational Button is pressed to enter the Main Menu 
where all control system menus are accessed. See Table 3 for a list 
of control system menus.
Help: The right Operational Button is pressed to access instructions 
and explanations for user settings, Operating States, Status Icons, 
manufacturer’s web address, technical support phone number and 
service agent contact information.
Day/Time/Operating  Mode:  The  current  time  and  day  are 
also displayed on the Desktop Screen. “Clock Not Set” will be 
displayed until the time clock has been initially set. Day and Time 
are  adjusted  in  the  Economy  Mode  Setup  menu.  The  current 
Operating  Mode,  either  Normal  Mode  or  Economy  Mode,  is 
displayed beneath the day and time.
Discreet Menu Contact Information: From the Desktop Screen 
press and hold down the middle (unmarked) Operational Button for 
30 seconds and then release it. This will launch a discreet menu 
where personalized contact information can be entered. Installing 
contractors and/or service agents can enter their company name 
and telephone number. This contact information will be displayed 
with all Fault and Alert messages.
Icon
descrIptIon
Water temperature in the tank has fallen. Shaded area of the animated thermometer icon will rise and fall in 
response to water temperature in the storage tank as sensed from the immersion Temperature Probe.
Water temperature in the tank has reached the Operating Set Point. Shaded area of the animated thermometer 
icon  will  rise  and  fall  in  response  to  water  temperature  in  the  storage  tank  as  sensed  from  the  immersion 
Temperature Probe.
The control is unable to initiate a heating cycle. This will happen whenever a Fault condition is detected by the 
control system or when either of the two Enable/Disable circuits are open circuits.
The control system is in Heating Mode and has energized the electromagnetic contactor coils for at least one bank 
of heating elements. This animated icon DOES NOT indicate current has been sensed from the heating elements, 
only that there is a call for heat present and the control system has initiated heating operation.
Heating elements icon for a water heater equipped with 1 Bank of heating elements. Each circle represents one 
heating element. Each diagonal row of 3 elements = 1 Bank of elements. Open circles represent heating elements 
the control system has not energized and is not sensing electrical current from.
Heating elements icon for a water heater equipped with 2 Banks of heating elements. Each circle represents one 
heating element. Each diagonal row of 3 elements = 1 Bank of elements. Open circles represent heating elements 
the control system has not energized and is not sensing electrical current from.
Heating elements icon for a water heater equipped with 3 Banks of heating elements. Each circle represents one 
heating element. Each diagonal row of 3 elements = 1 Bank of elements. Open circles represent heating elements 
the control system has not energized and is not sensing electrical current from.
Heating elements icon for a water heater equipped with 3 Banks of heating elements. Each circle represents one 
heating element. Each diagonal row of 3 elements = 1 Bank of elements. Filled circles represent heating elements 
the control system has energized AND is sensing electrical current from.
Heating elements icon for a water heater equipped with 3 Banks of heating elements. Each circle represents one 
heating element. Each diagonal row of 3 elements = 1 Bank of elements. Open circles with an X represent heating 
elements the control system has energized that it IS NOT sensing electrical current from.
The control has detected/declared a Fault Condition. Fault message details can be viewed in the Current Fault 
menu. Heating operation is discontinued (locked out) until the condition that caused the fault is corrected. Power to 
the water heater must be cycled off and on to reset the control system. Note; cycling power will not reset the control 
system if the condition that caused the fault has not been corrected.
The control has detected/declared an Alert Condition. The water heater will continue to operate during an Alert 
Condition but there is an operational condition that requires the attention of a Qualified Service Agent. Alert message 
details can be viewed in the Current Alert menu.
taBle 1 status Icons.