T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
11
63-4355—4
CAUTION
Possible Equipment Damage.
Fan must be running when system is operating.
Heat pump and electric heat systems must be 
configured correctly in Installer Setup 2 to prevent 
equipment damage caused by the system running 
without the fan.
IMPORTANT
Only configurable numbers are shown on the device. 
Example: If the thermostat does not have a system 
key, Installer Setup number 12 will not be displayed. 
Review Table 7 
factory settings and mark any 
desired changes in the Actual Setting column. When 
the Installer Setup is complete, review the settings to 
confirm that they match the system.
Table 7. Thermostat Installer Setup Options.
Select
Installer Setup 
Number 
(Press Unoccupied 
Temp to change)
Factory Setting
Other Choices 
(Press  or  to change)
Actual 
Setting
Display
Description
Display
Description
Not used
1
Fan operation
a
2
0
Conventional applications where 
equipment controls fan operation 
in heat mode.
1
Electric heat applications where thermostat 
controls fan operation in heat mode.
Output stages of 
heating
3
Subbase 
dependant
Stages of heat.
0, 1, 2, 
or 3
0: No heating.
1: One stage of heat.
2: Two stages of heat.
3: Three stages of heat.
Heating cycle rate
4
4
Stage 1: 4 cph.
3, 6, 8 or 
9
3: 3 cph (hot water systems or high 
efficiency furnaces).
6: 6 cph (conventional systems).
8: 8 cph (conventional systems).
9: 9 cph (electric heat systems).
5
4
Stage 2: 4 cph.
6
4
Stage 3: 4 cph.
7
4
Emergency heat relay is on 
continuously. Highest stage of 
heat cycles at 4 cph (Q7300C or D 
only).
Cooling output 
stages
8
Subbase 
dependant
Stages of cooling.
0, 1, 2 or 
3
0: No cooling.
1: One cooling stage.
2: Two cooling stages.
3: Three cooling stages.
Cooling cycle rate
9
4
Stage 1: 4 cph.
3
3: 3 cph.
10
4
Stage 2: 4 cph.
11
4
Stage 3: 4 cph.
System setting 
adjustment 
(models with 
System key)
12
Model 
dependant
System selection.
0, 1 or 2 0: System setting key is operational.
1: Auto setting disabled.
2: Auto only setting.
Not used
13
Degree 
temperature 
display
14
0
Temperature displayed in °F.
1
Temperature displayed in °C.
Displaying 
temperature 
(T7300F only).
15
0
Temperature displayed.
1
Temperature not displayed.
Clock format.
16
0
12-hour clock format.
1
24-hour clock format.
Intelligent Fan™ 
operation.
17
2
Fan operates continuously in 
Occupied and recovery modes. 
Fan operates with call for heat or 
cool in Unoccupied mode.
0 or 1
0: Fan operates only with call for heat or 
cool (Occupied and Unoccupied modes).
1: Fan operates continuously in Occupied 
mode. Fan operates with call for heat or 
cool in Unoccupied mode.
Auxiliary contact 
operation.
18
0
0: Time of day contact.
1
1: Economizer contacts.
a
Number 2 must be set to 1 to extend fan operation.
b
Number 22 must be set to 1 and remote sensor(s) must be installed.