T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
63-4355—4
12
Extended fan 
operation in heat
a
 
(T7300F only).
19
0
No extended fan operation after 
call for heat ends.
1
Fan operation extended 90 sec after call for 
heat ends.
Extended fan 
operation in 
cooling 
(T7300F only).
20
0
No extended fan operation after 
the call for cooling ends.
1
Fan operation is extended 90 seconds after 
the call for cooling ends.
Fan key 
adjustment 
(models with Fan 
key).
21
0
Fan setting key operational.
1
Fan setting key is Auto only.
Remote sensing.
22
0
Remote sensing not activated.
1
Remote sensing activated.
Temperature 
averaging network
b
 
(T7300F only).
23
0
Temperature averaging disabled.
1
Temperature averaging between local 
sensor and remote sensor(s) activated.
Not used.
24
Keypad lockout 
level (keypad 
lockout enabled/
disabled by DIP 
switch 1 on 
thermostat back). 
(T7300F only)
25
0
No lockout.
1, 2 or 3 1: Lockout all thermostat keys except 
system and fan settings, temporary 
setpoint, clock and day adjustments, 
increase ▲ and decrease ▼.
2: Lockout all keys except Set Current Day/
Time, increase ▲ and decrease ▼.
3: Lockout all keys except Temporary 
Occupied and Set Current Day/Time (for 
clock, day adjustment).
Duration of 
temporary 
override.
26
3
3: Three hour override.
1, 8 or 
12
1: One hour override.
8: Eight hour override.
12: Twelve hour override.
Not used.
27 through 29
Deadband 
(T7300F only).
30
2
Heating and cooling setpoints can 
be set no closer than 2°F (1.1°C).
3 - 10
Heating and cooling setpoints can be set no 
closer than the chosen value.
Interstage control 
point (T7300F, 
Q7300C,D only).
31
0
Disabled.
1 - 12
Temperature must change more than 
chosen value before system calls for next 
stage. (Example: heat setpoint: 68°F (20°C), 
interstage setting: 2°F (1.1°C), temperature 
is 65.5°F (18.5°C). Second stage turns on, 
brings temperature to 66°F (19°C) and turns 
off. Heat pump continues to run until setpoint 
is reached.
Minimum on- time 
(T7300F). 
32
2
2-minute minimum on- time for 
heating and cooling.
0 or 1
No minimum on-time or 1-minute minimum 
on-time for heating and cooling.
Minimum 
compressor off-
time.
33
4
4-minute minimum compressor 
off-time.
0, 1, 2, 3 
or 5
Minimum number of minutes (0 through 5) 
compressor is off between compressor calls.
Temperature heat 
range stops 
(T7300F).
34
90
Highest heat setpoint.
40 to 89 Heat setpoint temperature range (1°F 
increments).
Temperature 
cooling range 
stops (T7300F).
35
45
Lowest cooling setpoint.
46 to 99 Temperature range (1°F increments) for 
cooling setpoint.
Not used.
36
Table 7. Thermostat Installer Setup Options. (Continued)
Select
Installer Setup 
Number 
(Press Unoccupied 
Temp to change)
Factory Setting
Other Choices 
(Press  or  to change)
Actual 
Setting
Display
Description
Display
Description
a
Number 2 must be set to 1 to extend fan operation.
b
Number 22 must be set to 1 and remote sensor(s) must be installed.