York 00497VIP Manuale Utente

Pagina di 112
YORK INTERNATIONAL
10
  • 
At  the  chiller/condenser  control  panel  that  uses 
a  rotary  switch  to  set  the  ID,  use  a  small  screw 
driver to rotate the rotary switch so that the arrow 
points at the number that coincides with the Unit’s 
Identification number (ID#). Unit 1 - Unit 8 coincide 
to  rotary  switches  0  -  7.  Otherwise  program  the 
panel’s ID through keypad entry.
Never  skip  an  ID#.  For  example,  if 
you have four units then they must be 
identified from ID#0 - ID#3.
  • 
At the chiller/condenser unit’s control panel, select 
the type of control mode. Select REMOTE only if 
remote control is desired. Select LOCAL to only 
monitor this unit.
  • 
From the Comms Screen  of the OptiView RCC, 
enter the RCC Poll Time. This is how often (time 
in seconds) to request data. This time should be set 
long enough to allow for receiving the data. 
WIRING
A communications cable must connect the chiller to the 
remote panel. This cable should be a three-conductor 
with foil shield and drain wire, 20 awg or larger sized 
wire,  300v,  80  Deg.  C,  U.L.  Style  2464,  U.L.  listed 
and  CSA  approved. Three  sources  are Alpha  5463, 
Belden 9364, or Quabbin 0220. The cable length (sum 
of  lengths  of  all  cables)  must  not  exceed  4000  ft. 
(1219 m.).
Never run the communication cable in 
close proximity to any power wiring. 
For best results, it should be run in 
dedicated,  grounded  conduit.  See 
Proper Installation Practices.
SECTION 2 – INSTALLATION
MOUNTING
Mount  the  Remote  Control  Center  at  a  level  that 
provides for easy viewing of the color graphic display 
by all users. Securely mount it at the desired location. 
The panel may be mounted away from the chiller as far 
as 4000 ft. (1219 m.) of wiring will allow.
INSTALLATION CHECKLIST
(Reference Fig. 2 for wiring)
 
  A communications cable must connect the OptiView 
RCC to the chiller/condenser control panel. This 
cable should be a three-conductor with foil shield 
and drain wire, 20 awg or larger wire, 300v, 80 Deg. 
C, UL Style 2464, UL listed and CSA approved. 
Three  sources  are Alpha  5463,  Belden  9364,  or 
Quabbin 0220. The cable length (sum of lengths of 
all cables) must not exceed 4000 ft. (1219 m.). The 
cable is user supplied.
  • 
Obtain ferrite (part number 025-35154-000) from 
the  cloth  bag  found  in  the  OptiView  RCC  and 
install it as shown on Fig. 2. This must be installed 
to meet FCC and CE requirements.
  • 
Make sure that the Transient Voltage Suppressors are 
installed at J12. One is installed from “+” to “GND” 
and one is installed from “-” to “GND”.
  • 
At J12 of the OptiView RCC, red wire on RS485(+), 
black wire on RS485(-) and white wire on Ground. 
  • 
At the OptiView RCC, connect the shield to the 
panel.
  •
  Use a tie wrap between the J12 connector and the 
Ferrite (part number 025-35154-000) to secure the 
shielded cable to the OptiView RCC. The tie wrap 
can help prevent the wires from being accidentally 
pulled out of the J12 connector by someone working 
in the panel or by the weight of the ferrite. 
  • 
Install a LAN transient protection module at the 
chiller/condenser  control  panel  and  connect  the 
cable according to the type of control panel.
  •
  Make sure the correct EPROM is installed at the 
chiller/condenser control panel(s). See Table 1.
  • 
From the Setpoints Screen of the OptiView RCC, 
enter the Number of Units Connected (Maximum 
value allowed is 8). 
Installation