York 00497VIP Manuale Utente

Pagina di 112
FORM 50.40-OM2
101
YORK INTERNATIONAL
SERIAL INPUTS / OUTPUTS TESTS
This diagnostic is used to verify correct operation of 
the Serial Data Ports. There is a test for each of the 
five  Serial  Data  Ports.  Each  RS-232  port  (COM  1, 
2  and  4b)  is  tested  by  transmitting  serial  test  data 
from outputs to inputs of each port. Both the transmit 
and receive functions as well as the control lines are 
tested. The RS-485 ports (COM 3 and 4a) are tested 
by transmitting serial test data from one RS-485 port 
to  another. The TX/RX  opto-coupled  port  (COM  5) 
is tested by transmitting serial test data from the TX 
output to the RX input. If the received data matches the 
transmitted data, PASS is displayed, indicating the serial 
port is OK. Otherwise, FAIL is displayed, indicating 
the serial port is defective. Prior to performing each 
test, the Service Technician must install a wire loop-
back connection as described below. Refer to Section 
5  and  Figure  35  of  this  book  for  description  of  the 
Serial data Ports.
PROCEDURE
  1.  Using  small  gauge  wire,  fabricate  loop-back 
connections  and  install  as  follows  for  each 
port  to  be  tested.  Failure  to  install  the  loop-
back connection or configure the Microboard 
Program jumper as noted will result in a FAIL 
outcome for the test.
 
 
From   
To
  COM 1 
J2-4 (TX) 
J2-3 (RX)
 
   
J2-5 (DTR) 
J2-2 (DSR)
  
 
From   
To
COM 2  
J13-5 (TX) 
J13-3 (RX)
 
   
J13-7 (DTR)  J13-1(DCD) & 
 
   
 
 
J13-2(DSR)
 
   
J13-4 (RTS) 
J13-6 (CTS) &
 
   
 
 
J13-8 (RI)
 
 
RS-485  
From   
To
(COM   
J12-3 (+) 
J11-3 (+)
3 & 4a)  
J12-2 (-) 
J11-2 (-)
Microboard Program Jumper JP27 must be installed 
in position 1 & 2.
 
   
From   
To
COM 4b 
J2-7 (GTX) 
J2-6 (GRX)
Microboard Program Jumper JP27 must be installed 
in position 2 & 3
  2.  After  connecting  appropriate  loop-back  con-
nections  above,  press  the  appropriate  key  to 
initiate the desired test. An LED will illuminate 
indicating the test is in progress. If it is desired 
to terminate the test, press the CANCEL TEST 
key. Test data is sent from an output to an input 
as  described  below. At  the  completion  of 
each  test,  if  the  data  received  matches  the 
data  sent,  the  Serial  Port  operates  properly 
and  PASS  is  displayed.  Otherwise,  FAIL  is 
FIG. 52
00530VIPC
5