York 00497VIP Manuale Utente

Pagina di 112
YORK INTERNATIONAL
58
DISPLAY MESSAGES
A title bar will be displayed on all screens. This title 
bar will contain the OptiView Remote Control Center 
date and time on all RCC screens. This title bar will 
contain the Chiller/Condensing unit’s date and time on 
all unit screens. On the Home Screen the message will 
read  “YORK  REMOTE  CONTROL  CENTER”.  On 
all other screens it will contain the unit selected and 
either the chiller type or will be based on the number 
of compressors of that unit.
When a unit has been selected the title bar will display 
a  dual  message  on  every  screen. The  first  message 
will display the Unit Selected in the format “Unit x”, 
where x is the number (1 – 8) of the unit selected. The 
second message will display the chiller type, whether 
it is a “Screw”, “Recip” or “Scroll” and the number 
of compressors. 
On the Unit Screen and all System Screens the title bar 
contains another message called a Status. The current 
status of each unit is displayed in this message. These 
messages will include running status, cooling demand, 
fault status, external cycling device status, load limiting 
and  anti-recycle  timer  status,  etc. A  System  Status 
message and a Unit Status message are never displayed 
simultaneously. A  single  message  is  displayed  for  a 
Unit Status message, while a separate System Status 
message will display for each system on multi-circuit 
units.
Status  messages  fall  into  the  categories  of  warning, 
safety, and normal with each of the categories discussed 
following:
 •  
Warning messages are denoted by yellow message 
text. A warning message is shown for any special 
running  condition  and  for  all  unit  warnings. 
Any kind of load limiting would be an example 
of  a  warning  message. An  incorrect  refrigerant 
programmed warning would also be an example 
of a warning message.
 • 
  Safety messages are denoted by red message text. 
A safety message is shown for any type of safety 
shutdown, lock-out, or run inhibit. High discharge 
pressure would be an example of a safety shutdown 
message.
 •  
Normal  messages  are  denoted  by  green  text. 
A  normal  message  is  shown  for  any  non-fault 
normal  condition. The  compressor  running  and 
no cooling load messages would be examples of 
normal messages.
Note  that  there  are  two  types  of  shutdowns.  If  the 
chiller shuts down on a SAFETY shutdown, it requires 
the operator to perform a manual reset at the keypad. A 
NORMAL shutdown occurs from a properly requested 
or  scheduled  shutdown.  The  event  that  caused  the 
shutdown is displayed on the Status Line.
STATUS MESSAGES
Status messages will be much like those displayed at 
the chiller panel. Explanation of these displays will be 
outlined  in  the  Installation  Manual  for  each  specific 
chiller. Subtle differences may be noted in the exact 
wording displayed versus the display which is shown 
on  the  chiller  panel. An  example  of  this  is  apparent 
in  the  anti-recycle  and  anti-coincidence  timers.  In 
the case of these messages, the chiller control panel 
indicates actual time left on the timers. The OptiView 
Remote  Control  Center  will  only  indicate  that  the 
timers are “Active”. 
The new message “Loss of Communications” indicates 
that  the  communications  link  between  the  chiller 
control panel and the OptiView Remote Control Center 
has been lost. This loss of communications is normally 
a result of disconnecting the RS-485 communications 
cable between the two panels or the loss of power to 
the chiller control panel.
If communications is lost and not re-established, local 
chiller  setpoints  will  command  chiller  control  after 
5 minutes.
In  addition  to  the  chiller  status  messages  there  are 
the  Optiview  Remote  Control  Center  general  status 
messages  that  are  displayed  on  a  single  line  on  the 
Home Screen for each chiller. See the description of 
the Home Screen in this manual.
SAFETY SHUTDOWN MESSAGE
“WATCHDOG – SOFTWARE REBOOT”
The  Microboard’s  software  Watchdog  initiated  a 
Microprocessor reset because it detected that a portion 
of the chiller operating Program was not being executed. 
The  result  of  this  reset  is  a  Safety  shutdown  and 
re-initialization  of  the  Program.  This  is  generally 
indicative  of  a  severe  electrical  power  disturbance 
or impending Microboard Failure. The chiller can be 
started after the COMPRESSOR switch is placed in 
the Stop-Reset (O) position.
Operation