3) Connection to PLC (when external thermal O/L relay is used)
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
12 
V
 
U
W
13 
FWD 
11 
X1
 
REV
 
CM
 
X3
 
30C
 
30B
 
30A
 
X2 
(THR)
 
L2/S
 
L1/R 
L3/T
 
P
P(+)
 
N(-)
 
P(+)
 
M
FM 
C1 
X3
 
EXT
 
INT
 
PLC
 
MCCB 
 Frequency setting POT (VR) 
 
 
+10Vdc
 
250oh
22koh
Pulse output 
0V
 
0V
 
Analog monitor
 
Alarm output for any fault
 
To 11 terminal 
Analog meter
 
+24 to +27Vdc
 
P L C 
24dcV
 
External thermal O/L relay
 
External thermal O/L relay
 
To X2    To CM terminal
terminal  
 
To ground terminal
 
To ground terminal
 
SW7 
2
 
1
 
*1   Connect the X3 terminal to the PLC power supply of 24Vdc in common and do not connect the CM and 11 
terminals to the PLC common.  This is to prevent the FWD and REV terminals from turning on due to sneak 
path current if the PLC power supply is turned off. 
*2   With this connection, because the internal power of the drive can be supplied to the external thermal O/L 
relay, OH2 trip is not activated by PLC power-off with the drive turned on. 
*3   Set SW7 switch 1 to INT and 2 to PLC. 
*4 
 When the X3 terminal is used as the PLC terminal, no function that can be set with E03 can    
be used.  The X3 terminal is dedicated to the PLC.
 
24Vdc : 
PLC power supply
 
Figure 2-3-11  Connection example of PLC terminal (using THR function terminal) 
G 
G 
4.7k
Ω
 
250
Ω
 
22k
Ω
 
To X2    To CM terminal
terminal  
 
3-phase 230V 
input series
 
200 to 230V  
50/60Hz 
Single-phase 
230V input series
200 to 240V  
50/60Hz 
L1/L 
L2/N 
MCCB 
PLC
 
X3
 
INT
 
EXT
 
STOP 
RUN
 
PRG 
RESET
 
FUNC 
D ATA
 
3~
 
FUSE 
FUSE