TROUBLESHOOTING
Confirmation and check
When a fault occurs in the air conditioner, the check
code and the indoor unit No. will appear on the display
part of the remote controller.
The check code will only be displayed while the unit is
in operation.
If the display disappears, operate the air conditioner
according to the following “Confirmation of error
history” for confirmation.
Confirmation of error history
When a fault occurs in the air conditioner, the error
history can be confirmed with the following procedure.
(The error history is stored in memory and can contain
up to 4 errors).
This history can be confirmed from either the operating
status or the stop status.
CODE No.
UNIT   No.
R.C.
No.
Check code
Indoor unit No. in which 
an error occurred
3
2
1
ON / OFF
FAN
TEMP.
SWING/FIX
TIME
MODE
VENT
UNIT
SET
CL
FILTER
RESET TEST
TIMER SET
Procedure
1
2
3
Description
When pushing the 
SET
 and 
TEST
 buttons simultaneously for 4 seconds
or more, the display similar to the one shown in the figure to the right
will appear.
If [Service Check] is displayed, the fault code will be stored in the
error history mode.
• 01 (Order of error history) is displayed in CODE No. window.
• Check Code is displayed in the CHECK window.
• The indoor unit address, where the fault has occurred will be
displayed in the UNIT No. window.
When pushing the 
TEMP.
 buttons, the error history stored within the memory will be displayed in
chronological order.
The numbers displayed within the CODE No. window can vary between 1 and 4. 1 being the most recent fault
and 4 being the oldest.
CAUTION
Do not push the 
CL
 button as this will erase all of the error history for that indoor unit.
After confirmation, push the 
TEST
 button. This will return the display back to its original mode.
CODE No.
UNIT   No.
R.C.
No.
Check method
On the remote controller (Main remote controller, Central control remote controller) and the interface P.C. board of
the outdoor unit, a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C.
board) operation is provided. Therefore the operation status can be known. Using this self-diagnosis function, a fault
and the location of this fault within the air conditioning system can be located, as shown in the table below.
Check code list
The following list shows each check code. Find the check contents from the list according to part to be checked.
• In case of a fault from the indoor remote controller: See “Main remote controller display” in the list.
• In case of a fault from the outdoor unit: See “Outdoor 7-segment display” in the list.
• In case of a fault from the indoor unit with a wireless remote controller:
See “Sensor block display of receiving unit” in the list.
Terminology
IPDU : Intelligent Power Drive Unit
¡
  : Lighting,  
¤
 : Flashing,  
l
 : Goes off
ALT. : Flashing is alternately when there are two flashing LED.
SIM : Simultaneous flashing when there are two flashing LED.
Check code
Wireless remote controller
Outdoor 7-segment display
Sensor block display
of receiving unit
Main
remote
controller
display
Auxiliary code
Operation
Timer
Ready
Flash
Check code name
Judging device
E01
¤
l
l
Communication error between indoor and remote
controller (Detected at remote controller side)
Remote controller
E02
¤
l
l
Remote controller transmission error
Remote controller
E03
¤
l
l
Communication error between indoor and remote
controller (Detected at indoor side)
Indoor
E04
l
l
¤
Communication circuit error between indoor/outdoor
(Detected at indoor side)
Indoor
E06
E06
No. of indoor units in which sensor has
been normally received
l
l
¤
Decrease of No. of indoor units
I/F
E07
l
l
¤
Communication circuit error between indoor/outdoor
(Detected at outdoor side)
I/F
E08
E08 Duplicated indoor addresses
¤
l
l
Duplicated indoor addresses
Indoor / I/F
E09
¤
l
l
Duplicated main remote controllers
Remote controller
E10
¤
l
l
Communication error between indoor MCU
Indoor
E12
E12
01: Indoor/Outdoor communication
02: Communication between outdoor units
¤
l
l
Automatic address start error
I/F
E15
E15
l
l
¤
Indoor is nothing during automatic addressing
I/F
E16
E16
00: Capacity over
01 ~: No. of connected units
l
l
¤
Capacity over / No. of connected indoor units
I/F
E18
¤
l
l
Communication error between indoor units
Indoor
E19
E19
00: Header is nothing
02: Two or more header units
l
l
¤
Outdoor header units quantity error
I/F
E20
E20
01: Outdoor of other line connected
02: Indoor of other line connected
l
l
¤
Other line connected during automatic address
I/F
E23
E23
l
l
¤
Sending error in communication between outdoor units
I/F
E25
E25
l
l
¤
Duplicated follower outdoor addresses
I/F
E26
E26
No. of outdoor units which received signal
normally
l
l
¤
Decrease of No. of connected outdoor units
I/F
E28
E28 Detected outdoor unit number
l
l
¤
Follower outdoor unit error
I/F
E31
E31
01: IPDU1 error
02: IPDU2 error
03: IPDU1, 2 error
04: Fan IPDU error
05: IPDU + Fan IPDU error
06: IPDU2 + Fan IPDU error
07: All IPDU error
l
l
¤
IPDU communication error
I/F