Toshiba MMU-AP0121MH Manuale Di Servizio

Pagina di 117
32
9
TROUBLESHOOTING
Check code
Wireless remote controller
Outdoor 7-segment display
Sensor block display
of receiving unit
Main
remote
controller
display
Auxiliary code
Operation
Timer
Ready
Flash
Check code name
Judging device
F01
¤ ¤
l
ALT
Indoor TCJ sensor error
Indoor
F02
¤ ¤
l
ALT
Indoor TC2 sensor error
Indoor
F03
¤ ¤
l
ALT
Indoor TC1 sensor error
Indoor
F04
F04
¤ ¤
¡
ALT
TD1 sensor error
I/F
F05
F05
¤ ¤
¡
ALT
TD2 sensor error
I/F
F06
F06
¤ ¤
¡
ALT
TE1 sensor error
I/F
F07
F07
¤ ¤
¡
ALT
TL sensor error
I/F
F08
F08
¤ ¤
¡
ALT
TO sensor error
I/F
F10
¤ ¤
l
ALT
Indoor TA sensor error
Indoor
F12
F12
¤ ¤
¡
ALT
TS1 sensor error
I/F
F13
F13
01: Comp. 1 side
02: Comp. 2 side
¤ ¤
¡
ALT
TH sensor error
IPDU
F15
F15
¤ ¤
¡
ALT
Outdoor temp. sensor miscabling (TE, TL)
I/F
F16
F16
¤ ¤
¡
ALT
Outdoor pressure sensor miscabling (Pd, Ps)
I/F
F23
F23
¤ ¤
¡
ALT
Ps sensor error
I/F
F24
F24
¤ ¤
¡
ALT
Pd sensor error
I/F
F29
¤ ¤
l
SIM
Indoor other error
Indoor
F31
F31
¤ ¤
¡
SIM
Indoor EEPROM error
I/F
H01
H01
01: Comp. 1 side
02: Comp. 2 side
l
¤
l
Compressor break down
IPDU
H02
H02
01: Comp. 1 side
02: Comp. 2 side
l
¤
l
Magnet switch error
Overcurrent relay operation
Compressor trouble (lock)
MG-SW
Overcurrent relay
IPDU
H03
H03
01: Comp. 1 side
02: Comp. 2 side
l
¤
l
Current detect circuit system error
IPDU
H04
H04
l
¤
l
Comp 1 case thermo operation
I/F
H06
H06
l
¤
l
Low pressure protective operation
I/F
H07
H07
l
¤
l
Oil level down detective protection
I/F
H08
H08
01: TK1 sensor error
02: TK2 sensor error
03: TK3 sensor error
04: TK4 sensor error
l
¤
l
Oil level detective temp sensor error
I/F
H14
H14
l
¤
l
Comp 2 case thermo operation
I/F
H16
H16
01: TK1 oil circuit system error
02: TK2 oil circuit system error
03: TK3 oil circuit system error
04: TK4 oil circuit system error
l
¤
l
Oil level detective circuit error
Magnet switch error
Overcurrent relay operation
I/F
MG-SW
Overcurrent relay
L03
¤
l
¤
SIM
Indoor center unit duplicated
Indoor
L04
L04
¤
¡
¤
SIM
Outdoor line address duplicated
I/F
L05
¤
l
¤
SIM
Duplicated indoor units with priority
(Displayed in indoor unit with priority)
I/F
L06
L06
No. of indoor units with priority
¤
l
¤
SIM
Duplicated indoor units with priority
(Displayed in unit other than indoor unit with priority)
I/F
L07
¤
l
¤
SIM
Group line in individual indoor unit
Indoor
L08
L08
¤
l
¤
SIM
Indoor group/Address unset
Indoor, I/F
L09
¤
l
¤
SIM
Indoor capacity unset
Indoor
L10
L10
¤
¡
¤
SIM
Outdoor capacity unset
I/F
L20
L20
¤
¡
¤
SIM
Duplicated central control addresses
Indoor
L28
L28
¤
¡
¤
SIM
Over No. of connected outdoor units
I/F
L29
L29
01: IPDU1 error
02: IPDU2 error
03: IPDU3 error
04: Fan IPDU error
05: IPDU1 + Fan IPDU error
06: IPDU2 + Fan IPDU error
07: All IPDU error
¤
¡
¤
SIM
No. of IPDU error
I/F
L30
L30
Detected indoor address
¤
¡
¤
SIM
Indoor outside interlock
Indoor
L31
Extended I/C error
I/F
Error detected by TCC-LINK central control device
Terminology
TCC-LINK : TOSHIBA Carrier Communication Link.
Check code
Wireless remote controller
Outdoor 7-segment display
Sensor block display
of receiving unit
Main
remote
controller
display
Auxiliary code
Operation
Timer
Ready
Flash
Check code name
Judging device
P01
l
¤ ¤
ALT
Indoor fan motor error
Indoor
P03
P03
¤
l
¤
ALT
Discharge temp. TD1 error
I/F
P04
P04
01: Comp. 1 side
02: Comp. 2 side
¤
l
¤
ALT
High-pressure SW system operation
IPDU
P05
P05
01: Phase-missing detection
02: Phase error
¤
l
¤
ALT
Phase-missing detection /Phase error
I/F
P07
P07
01: Comp. 1 side
02: Comp. 2 side
¤
l
¤
ALT
Heat sink overheat error
IPDU, I/F
P10
P10 Detected indoor address
l
¤ ¤
ALT
Indoor overflow error
Indoor
P12
l
¤ ¤
ALT
Indoor fan motor error
Indoor
P13
P13
l
¤ ¤
ALT
Outdoor liquid back detection error
I/F
P15
P15
01: TS condition
02: TD condition
¤
l
¤
ALT
Gas leak detection
I/F
P17
P17
¤
l
¤
ALT
Discharge temp. TD2 error
I/F
P19
P19 Detected outdoor unit number
¤
l
¤
ALT
4-way valve inverse error
I/F
P20
P20
¤
l
¤
ALT
High-pressure protective operation
I/F
0
[ :  IGBT short
1
[ :  Fan motor position detective circuit error
3
[ :   Fan motor trouble
C
[
:  TH sensor temp. error
 (Heat sink overheat)
D
[ :  TH sensor error
P22
P22
E
[ :   Vdc output error
¤
l
¤
ALT
Outdoor fan IPDU error
IPDU
P26
P26
01: Comp. 1 side
02: Comp. 2 side
¤
l
¤
ALT
G-TR short protection error
IPDU
P29
P29
01: Comp. 1 side
02: Comp. 2 side
¤
l
¤
ALT
Comp position detective circuit system error
IPDU
P31
P31
¤
l
¤
ALT
Other indoor unit error (Group terminal unit error)
Indoor
Check code
Wireless remote controller
Outdoor 7-segment display
Sensor block display
of receiving unit
Central
control
device
indication
Auxiliary code
Operation
Timer
Ready
Flash
Check code name
Judging device
C05
Sending error in TCC-LINK central control device
TCC-LINK
C06
Receiving error in TCC-LINK central control device
TCC-LINK
C12
Batch alarm of general-purpose equipment control
interface
General-purpose equipment
I/F
Differs according to error contents of unit with occurrence of alarm
Group control branching unit error
P30
(L20 is displayed.)
Duplicated central control addresses
TCC-LINK