Hitachi SJ300-037HFE Manuale Utente

Pagina di 289
“A” Group: Standard Functions
Configur
ing Dr
iv
P
a
ra
meters
3–12
“A” Function
Run 
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)
A005 [AT] selection
Two options; select codes:
00 Select between [O] and 
[OI] at [AT]
01 Select between [O] and 
[O2] at [AT]
✘ ✘
00
00
00
>A005 AT
SELECT      O/OI
A006 [O2] selection
Three options; select codes:
00 No summing, [O2] and 
[OI]
01 Sum of [O2] and [OI], 
neg. sum (reverse speed 
reference) inhibited
02 Sum of [O2] and [OI], 
neg. sum (reverse speed 
reference) allowed
✘ ✘
00
00
00
>A006 O2
SELECT O2
A011 [O]–[L] input active 
range start frequency
The output frequency corre-
sponding to the voltage input 
range starting point
Range is 0.00 to 400.00 Hz
✘ ✔ 0.00 0.00 0.00
Hz
>A011 INPUT-O
EXS    0000.00Hz
A012 [O]–[L] input active 
range end frequency
The output frequency corre-
sponding to the voltage input 
range ending point
Range is 0.00 to 400.00 Hz
✘ ✔ 0.00 0.00 0.00
Hz
>A012 INPUT-O
EXE    0000.00Hz
A013 [O]–[L] input active 
range start voltage
The starting point for the 
voltage input range
Range is 0 to 100%
✘ ✔
0.
0.
0.
%
>A013 INPUT-O
EX%S        000%
A014 [O]–[L] input active 
range end voltage
The ending point for the 
voltage input range
Range is 0 to 100%
✘ ✔ 100. 100. 100.
%
>A014 INPUT-O
EX%E        100%
A015 [O]–[L] input start 
frequency enable
Two options; select codes:
00 Use A011 start value
01 Use 0 Hz
✘ ✔
01
01
01
>A015 INPUT-O
LEVEL      0Hz
A016 External frequency filter 
time constant
Range n = 1 to 30, where n = 
number of samples for avg.
✘ ✔
8.
8.
8.
Sam-
ples
>A016 INPUT
F-SAMP        08