FieldServer HCS-R Manuale Utente

Pagina di 17
FS-8700-127 Hanning & Kahl HCS-R Manual 
 
 
 
 
Page 7 of 17 
 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.FieldServer.com 
Tel: 408 262-2299   Fax: 408-262-2269   Toll_Free: 888-509-1970   email: support@FieldServer.com 
4.2. 
Client Side Connection Descriptions 
Section Title 
Connections 
Column Title 
Function 
Legal Values 
Port 
Specify  which  port  the  device  is 
connected to the FieldServer 
P1-P8
1
 
Protocol 
Specify protocol used 
HCS-R 
HCSR 
H&K HCS-R 
Baud* 
Specify baud rate 
9600 (Vendor limitation) 
Parity* 
Specify parity 
None (Vendor limitation) 
Data_Bits* 
Specify data bits 
8 (Vendor limitation) 
Stop_Bits* 
Specify stop bits 
1 (Vendor limitation) 
Handshaking* 
Specify hardware handshaking 
None (Vendor limitation) 
Poll_Delay* 
Time between internal polls 
0-32000 seconds, 0.05 seconds 
 
Example 
 
//    Client Side Connections 
 
Connections 
Port, 
Protocol, 
Baud, 
Parity, 
Handshaking, 
Poll_Delay 
P8, 
HCS-R, 
9600, 
None, 
 None, 
0.100s 
 
 
4.3. 
Client Side Node Descriptors 
Section Title 
Nodes 
Column Title 
Function 
Legal Values 
Node_Name 
Provide name for Node 
Up to 32 alphanumeric characters 
Node_ID 
HCS-R  station  address  of  physical 
server Node 
240 (Protocol limit) 
Protocol 
Specify protocol used 
HCS-R 
HCSR 
H&K HCS-R 
Connection 
Specify  which  port  the  device  is 
connected to the FieldServer 
P1-P8
1
 
 
Example 
 
//    Client Side Nodes 
 
 
 
 
Nodes 
 
 
 
Node_Name, 
Node_ID, 
Protocol, 
Connection 
PLC 1, 
240, 
HCS-R, 
P8 
 
                                                 
1
 
Not  all  ports  shown  are  necessarily  supported  by  the  hardware.  Consult  the  appropriate  Instruction 
manual for details of the ports available on specific hardware.