FieldServer HCS-R 사용자 설명서
FS-8700-127 Hanning & Kahl HCS-R Manual
Page 7 of 17
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com
Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com
4.2.
Client Side Connection Descriptions
Section Title
Connections
Column Title
Function
Legal Values
Port
Specify which port the device is
connected to the FieldServer
connected to the FieldServer
P1-P8
1
Protocol
Specify protocol used
HCS-R
HCSR
H&K HCS-R
HCSR
H&K HCS-R
Baud*
Specify baud rate
9600 (Vendor limitation)
Parity*
Specify parity
None (Vendor limitation)
Data_Bits*
Specify data bits
8 (Vendor limitation)
Stop_Bits*
Specify stop bits
1 (Vendor limitation)
Handshaking*
Specify hardware handshaking
None (Vendor limitation)
Poll_Delay*
Time between internal polls
0-32000 seconds, 0.05 seconds
Example
// Client Side Connections
Connections
Port,
Connections
Port,
Protocol,
Baud,
Parity,
Handshaking,
Poll_Delay
P8,
HCS-R,
9600,
None,
None,
0.100s
4.3.
Client Side Node Descriptors
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for Node
Up to 32 alphanumeric characters
Node_ID
HCS-R station address of physical
server Node
server Node
240 (Protocol limit)
Protocol
Specify protocol used
HCS-R
HCSR
H&K HCS-R
HCSR
H&K HCS-R
Connection
Specify which port the device is
connected to the FieldServer
connected to the FieldServer
P1-P8
1
Example
// Client Side Nodes
Nodes
Node_Name,
Node_ID,
Protocol,
Connection
PLC 1,
240,
HCS-R,
P8
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction