Appendix A.4. 
Panel Synchronization 
Manual synchronization is required.  When the “Reset” button on the panel is pressed  a message is 
transmitted to the FieldServer, which clears the data in the FieldServer.  After a reset the panel sends 
messages  to  report  all  abnormal  states.    When  all  these  messages  have  been  processed  the 
FieldServer and panel will be synchronized.  This process can be repeated at any time. 
 
Appendix A.5. 
What happens when the panel sends a Reset Message 
When  a  panel  sends  a  reset  message  the  driver  processes  every  single  Map  Descriptor,  looking  at 
the ‘Clear on Reset’ parameter (See section 4.4.2).  If the parameter is set to yes, then the driver sets 
all  the  Data  Array  elements  referenced  by  the  Map  Descriptor  to  zero  by  looking  up  the  Data  Array 
Name,  the  Data  Array  offset  and  the  length.    The  driver  also  clears  the  relevant  sections  of  a  Data 
Array specified with the DA_Bit_Name parameter. 
 
The  process can  take  some  time.    For  this  reason,  it  is  suggested  that  you  take  care  not  to  set  the 
Map Descriptor length to a value larger than necessary. 
 
Appendix A.5.1. 
Networked Panels. 
The driver can processes messages and store data from multiple panels provided that: 
• 
The  panels  are  connected  in  an  FCI  network  and  the  panels  are  configured  to  report  their 
events to the main panel 
• 
The main  panel  is  configured  to  send  the  Node  of  origin  in  a  message  preceding  the  event 
message.  Consult with FCI for information on how to achieve this. 
 
Example of message sent by a panel that  is networked.  The driver is dependent on seeing the 
node of event origin included in parenthesis before each event message. 
 
Node02: 
MISSING                                 Acclimate       L1S041 00:17:06 
01/01/06 
 
Node55: 1st Floor Lobby 
DISCONNECT RSTRD                        Ion Detector    L1S024 09:51:44 
01/15/06 
 
Local: 
FIRST ALARM                             Photo Detector  L1S001 09:24:52 
12/01/06 
 
 
The main panel is identified as ‘Local’.  The driver interprets this as Node_ID=0. 
 
To capture events from multiple networked panels a  Node  Descriptor  is required for each panel 
with the appropriate Node_ID.  Each Node requires a set of Map Descriptors.