Appendix B. Troubleshooting Tips 
Appendix B.1.  Address Errors 
If the driver produces BAD_ADDRESS stats then do the following  
  Read the notes on processing errors. You can see the last error response and a report 
of the MD's which received the error response in the error array.  
  Alternatively, take a log, open the ASCII version of the log and look for error messages. 
Error 2 is the response sent by the panel when it is polled for a point that doesn’t exist. 
Find the Error #2's n the log. Now look at the line which precedes the error. It is the poll. 
Look to see which point in being polled.  Now you know the c-p-s of the invalid point, edit 
the configuration and remove the MD which polls for data at that point. When you have 
finished  editing  the  configuration,  download  the  modified  file  and  reset  the  FS  for  the 
changes to take effect. 
 
Appendix B.2.  Driver Limitations 
  Other than being able to write through a Map Descriptor where the sim4100_func=’clist’ , 
write throughs are not supported by this driver.  
  Port expansion is not supported.