Appendix C. Error Messages 
Error Message 
Troubleshooting Tip 
Sim4100:#1 
<card><point><sub> 
invalid for ack. Read manual. 
The card-point-sub is being used to derive an array 
offset. The calculation requires division by the point 
& the sub and one or both of these values are zero. 
Sim4100:#2 RTS has been asserted for 
too  long.  Extend  timer,  check  cable 
uses RTS/CTS or reconfig 4100 device 
to suppress hardware handshaking 
If  RTS-CTS  handshaking  has  been  used  then  this 
message  is  produced  if  the  driver  finds  that  the 
RTS has been asserted by the slave device for too 
long. The timeout is hard coded at 2.0s. 
Sim4100:#3  sim4100_chan_init()  Init 
with null chan. 
Requires support from FieldServer Technologies. 
Sim4100:#4  Unknown  sim4100_func  in 
csv <nnn> 
The  driver  has  found  a  value  for  a  sim4100_func 
keyword that it does not recognize. Check the CSV 
file and read Appendix A.2 of this manual for a list 
of legal keywords. 
Sim4100:#5 Use Ackall function. 
The sim4100_func keyword has been assigned the 
value  'ack'  but  a  card-point-sub  has  not  been 
specified.  It  would  be  better  to  use  the  ackall 
function instead. 
Sim4100:#6  ack/ackall/seta/setd  must 
be a write. 
You  cannot  use  the  rdbc  function  with  these 
keywords. Use a wrbc instead. 
Sim4100:#7 
disable/restart/list 
not 
implemented 
You  cannot  use  these  keywords  at  the  present 
time.  If  you  require  one  of  these  functions 
implemented call FieldServer Technologies. 
Sim4100:#8  Func=Clistall/Clist,  wrbc 
not allowed 
These keywords must be used with a rdbc instead. 
Sim4100:#9 
Write 
ack 
was 
not 
expected. 
Please 
report 
this 
error 
to 
FieldServer 
Technologies. 
Sim4100:#10 
Invalid 
point 
status 
<s><v><a>=(Hex)<%x><%x><%x> 
<%c><%c><%c> 
Please  report  his  message  to  FieldServer 
Technologies noting the values in braces. 
Sim4100:#11.  Error.  Array  too  short. 
rqd=  %d( 
max=  %d) 
act=  %d. 
MapDesc=  <%s>  Data  Abandoned! 
Subsequent msgs suppressed! 
Check the CSV file Data Array lengths. 
Sim4100:#12 Error. 
Incoming data is being abandoned. 
Subsequent message supressed! 
Check  the  CSV  file;  there  was  no  matching  Map 
Descriptor for a message. 
Sim4100:#13  FYI.  Login  Function  not 
Implemented. 
Please  contact  FieldServer  Technologies  if  you 
would like this feature implemented.