Toshiba W7 Manuale Utente

Pagina di 167
W7 ASD Installation and Operation Manual
147
Alarms
 lists the alarm codes that may be displayed during operation of the W7 ASD. Each alarm code 
listed is accompanied by a description and a possible cause. In the event that the source of the malfunction 
cannot be determined, contact your Toshiba Sales Representative for further information on the condition 
and for an appropriate course of action.
The active Alarm is displayed on the Frequency Command screen. Multiple active alarms are displayed 
one at a time and are scrolled at one-second intervals.
Table 11. W7 ASD Alarms.
EOI 
Display
Function
Description
Possible Causes
CM1
Comm1 Error
Internal communications error.
• Improperly programmed ASD.
• Improper communications settings.
• Improperly connected cables.
CM2
Comm2 Error
External communications error.
EMG
Emergency Off
Output signal from the ASD is 
terminated and a brake may be 
applied if so configured.
• Stop|Reset pressed twice at the EOI.
• EOFF command received remotely.
• ASD reset required.
MOFF
Main 
Undervoltage
Undervoltage condition at the 
 
3-phase AC input to the ASD.
• Low 3-phase utility voltage.
OC
Over Current
ASD output current greater than 
the parameter 
 setting.
• Defective IGBT (UV, or W).
• ASD output to the motor is connected incorrectly. 
Disconnect the motor and retry.
• ASD output phase-to-phase short.
• The ASD is starting into a spinning motor.
• Motor/machine jammed.
• Mechanical brake engaged while the ASD is starting or 
while running.
• Accel/Decel time is too short.
• Voltage Boost setting is too high.
• Load fluctuations.
• ASD operating at an elevated temperature.
*OH
Overheat
ASD ambient temperature 
excessive.
• ASD is operating at an elevated temperature.
• ASD is too close to heat-generating equipment.
• Cooling fan vent is obstructed (see 
).
• Cooling fan is inoperative.
• Internal thermistor is disconnected.
OJ
Timer
Run-time counter exceeded.
• Type Reset required; select Clear run timer.
* Reset ignored if active.