User Notification Codes
The User Notification codes appear on the Frequency Command screen while the associated function is 
active.
User Notification codes notify the user of active functions that are usually only momentary under normal 
conditions and are active for the duration of activation only. User notification events are not error 
conditions and only convey active system functions to the user.
Table 12
Trips/Faults
Trip is an ASD response to a Fault (though, Fault and Trip are sometimes used interchangeably). A 
Trip is a safety feature that disables the ASD system in the event that a subsystem of the ASD is 
malfunctioning.
Listed in 
 are the possible Faults that may cause a Trip and the possible causes. When a Trip is 
incurred the system displays the Fault screen. The Fault screen identifies the active Fault.
Table 13
EOI
Function
Description
Atn
Autotune Active
Atn indicates that the Autotune function is active. If the initial 
Autotune fails for any reason, an automatic retry is initiated if Other 
Motor 
is selected at 
parameter 
db or dbOn
DC Braking Active
This code conveys that the DC Injection function being carried out. 
The display shows db when braking and dbOn when the Shaft 
Stationary
 function is active.
Fault Screen Display
Possible Causes
Inverter (ASD) OL
• Acceleration time is too short.
• DC Injection current is too high.
• V/f setting needs to be adjusted.
• Motor running during restart.
• ASD or the motor is improperly matched to the application.
Autotuning Err
• Autotune readings that are significantly inconsistent with the configuration 
information.
• A non-3-phase motor is being used.
• Incorrect settings at parameter 
, o
• Using a motor that has a significantly smaller rating than the ASD.
• ASD output cabling is too small, too long, or is being housed in a cable tray with 
other cables that are producing an interfering EMF.
• Motor is running during the Autotune function.
Note:
The event that caused the Trip(s) must be corrected or must decrease to less than the threshold 
value required to cause the trip to allow for a Reset to be recognized. In the event of multiple 
active trips, the trip displayed will remain until all faults are corrected and all trips are cleared.