Toshiba W7 Manuale Utente

Pagina di 167
154
W7 ASD Installation and Operation Manual
Cable/Terminal Specifications
Installation should conform to the 2005 National Electrical Code Article 110 (NEC) (Requirements for 
Electrical Installations), all regulations of the Occupational Safety and Health Administration, and any 
other applicable national, regional, or industry codes and standards.
Note:
The following ratings are guidelines and shall not be the sole determining factor of the 
lug or wire size used with the W7 ASD. Application-specific applicables, wire insulation 
type, conductor material, and local and regional regulations are but a few of the 
considerations when selecting the actual lug and wire type to be used with the W7 ASD.
Note:
Cable/Terminal specifications are based on the rated current of the ASD.
Note:
Use only 75° C copper wire/cable for motor and power connections.
Note:
Input and Output power wires require shielding for CE compliance.
Note:
(*) Indicates that the item is one of a set of two parallel cables.
Note:
(**) Indicates that the item is one of a set of three parallel cables.
Model
MCCB 
Rating
(Amps)
Typical Wire/Cable Size (AWG or kcmil)
Lug Size Range
AM, FM, and II 
Terminals
Control 
Terminals
Input/Output 
Power
Wire-Size/
Lug-Capacity 
for Input 
Power 
Wire-Size/
Lug-Capacity 
for Output 
Power 
Recommended
W74600
100
20
(3-core shield)
18
(2-core shield)
3
8 to 3/0
16 to 1
W74750
225
1
3/0 to 350
10 to 1/0
W7410K
225
2/0
12 to 4/0
W7412K
225
3/0
W7415K
400
*1/0
2 to 500
*(6 to 250)
W7420K
400
*3/0
W7425K
600
*250
**(3/0 to 500)
*(1/0 to 500)
W7430K
600
*350
W7440K
800
*500