W7 ASD Installation and Operation Manual
15
Connecting the ASD
Refer to the section titled 
 and the section titled 
 before attempting to connect the ASD and the motor to electrical power.
System Grounding
Proper grounding helps to prevent electrical shock and to reduce electrical noise. The ASD is designed 
to be grounded in accordance with Article 250 of the 2005 NEC or Section 10/Part One of the 
Canadian Electrical Code (CEC).
The grounding conductor shall be sized in accordance with Article 250-122 of the 2005 NEC or Part 
One-Table 6
 of the CEC.
Note:
The metal of conduit is not an acceptable ground.
The input power, output power, and control lines of the system shall be run in separate metal conduits 
and each shall have its own ground conductor.
Power Connections
Connect the 3-phase input power to the input terminals of the W7 ASD at L1/RL2/S, and L3/T
Connect the output terminals T1/UT2/V, and T3/W of the W7 ASD to the motor. 
The input and output conductors and terminal lugs used shall be in accordance with the specifications 
listed in the section titled 
An inductor may be connected across terminals PA and PO to provide additional filtering. When not 
used, a jumper must be connected across these terminals (see 
Connect the input and output power lines of the W7 ASD as shown in 
Install a molded case circuit breaker (MCCB) or fuse between the 3-phase power source and the W7 
ASD
 in accordance with the fault current setting of the ASD and 2005 NEC Article 430.
Note:
In the event that the motor rotates in the wrong direction when powered up, reverse 
any two of the three ASD output power leads connected to the motor.
Figure 3. ASD/Motor connection diagram.
DANGER
DANGER