W7 ASD Installation and Operation Manual
17
Control Terminal Strip
I/O and Control
The W7 ASD can be controlled by several input types and combinations thereof, as well as operate 
within a wide range of output frequency and voltage levels. This section describes the ASD control 
methods and supported I/O functions.
The Control Terminal Strip PCBA (P/N 48570) supports discrete and analog I/O functions.
The Control Terminal Strip is shown in 
 and lists the names, the default 
settings (where applicable), and the descriptions of the input and output terminals.
 shows the basic connection diagram for the W7 ASD system.
Table 2. Control Terminal Strip default assignment terminal names and functions.
Terminal 
Name
Input/Output
Terminal Function
(default setting if programmable)
Circuit Config.
ST
Discrete Input
Standby (jumper to CC to operate the unit) — Multifunctional 
programmable discrete input (see 
 for further 
information on this terminal).
RES
Discrete Input
Reset — Multifunctional programmable discrete input.
F
Discrete Input
Forward — Multifunctional programmable discrete input.
R
Discrete Input
Reverse — Multifunctional programmable discrete input.
S1
Discrete Input
Preset Speed 1 — Multifunctional programmable discrete input.
S2
Discrete Input
Preset Speed 2 — Multifunctional programmable discrete input.
S3
Discrete Input
Preset Speed 3 — Multifunctional programmable discrete input.
S4
Discrete Input
Emergency Off — Multifunctional programmable discrete input.
RR
Analog Input
RR — Multifunction programmable analog input
 
(0.0 to 10 volt input — 0 to 80 Hz output). Reference CC.
RX
Analog Input
RX — Multifunctional programmable analog input 
 
(-10 to +10 VDC input — -80 to +80 Hz output). Reference CC.
II
Analog Input
II — Multifunctional programmable analog input (4 [0] to 20 mADC 
input — 0 to 80 Hz output) (see 
 for the location of the 
II terminal). Reference CC.
VI
Analog Input
VI — Multifunctional programmable analog input
 
(0 to 10 VDC input — 0 to 80 Hz output). Reference CC.
P24
DC Output
24 VDC @ 50 mA output.
PP
DC Output
PP — 10.0 VDC voltage source for the external potentiometer.
OUT1
Discrete Output Low Frequency — Multifunctional programmable discrete output. 
OUT2
Discrete Output Reach Frequency — Multifunctional programmable discrete output.
FP
Output
Frequency Pulse — an output pulse train that has a frequency which is 
based on the output frequency of the ASD.
AM
Output
Produces an output current that is proportional to the magnitude of the 
function assigned to this terminal (see 
FM
Output
FLC
Output
Fault relay (common).
FLB
Output
Fault relay (N.C.).
FLA
Output
Fault relay (N.O.).
CC
Control common (Do Not connect to Earth Gnd).
Discrete Input Terminals 
 On = connected to CC.
Analog Input terminals reference CC.