   nC1  ASD  Standard  Specifications
Model Range
1001P-1007  P
2002P-2022P
2001PL-2022PL
2002P-2022P
Input Voltage Rating
120 V/Single Phase
230 V/Single Phase
230 V/Three Phase
230 V/Single Phase with  
RFI / EMI Filter
KW Range
0.1 to 0.75 KW
0.2 to 2.2 KW
0.1 to 2.2 KW
0.2 to 2.2 KW
HP Range
1/8 to 1 HP
1/4 to 3 HP
1/8 to 3 HP 
1/4 to 3 HP
Overload Rating
150% for 60 Seconds
Input Voltage Tolerance
+10%, -15% 
+10%, -15% 
+10%, -15% 
+10%, -15%
Input Frequency Rating
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
Input Frequency Tolerance
± 5%
±5%
±5%
±5%
Output Voltage Rating
230 V, Three Phase
Color
Munsel 5Y8 / 0.5
Control System
Sinusoidal PWM Control
Output Voltage Range
Adjustable within a Range of 100 to 120% of Corrected Supply Voltage (200 V), Nonadjustable to any Voltage Higher than the Input 
Voltage
Output Frequency Range
0.5 to 200 Hz, Default Setting: 0.5 to 80 Hz, Max Frequency: 30 to 200 Hz
Minimum Frequency Step
0.1 Hz: Operation Panel Setting, 0.2 Hz: Analog Input (when the Max Frequency is 100 Hz)
Frequency Accuracy
Digital Setting: within ±0.5% of the Max Frequency (-10 to +50°C)
Analog Setting: within ±1.0% of the Max Frequency (25°C ± 10°C )
V/f Characteristics
V/f, Slip Frequency Compensation, Base Frequency, Base Frequency Voltage and Torque Boost  (Adjustable Amount)
Frequency Setting Signal
Internal Pot on the Front Panel, External Frequency Signal (Connectable to a Volume with a Rated Impedance of 3 to 10 kΩ),  
VI Terminal (Input Impedance: 42 kΩ (Voltage: 0 to 10 Vdc) or 250 Ω (Current: 4 to 20 mAdc)). Frequency can be Set Arbitrarily  
Using a Two Point Setting
Startup & Jump Frequency
Adjustable within a Range of 0.5 to 10 Hz; Up to 1 Frequency can be Adjusted Together with its Widths
PWM Carrier Frequency 
Selectable from among 2, 4, 8, 12, and 16 kHz (Standard Default Setting: 12 kHz or 4 kHz for Models with a Built-In EMI Noise Filter)
Accel/Decel Time
Two Selectable Accel/Decel Times Adjustable from 0.1 to 3000 seconds
Retry Operation
Selectable Number of Retries (Maximum 10 Times); If Protection Function is activated, Retry Function restarts after a main circuit check.
Electric Control
Charging of Capacitor (Deceleration Time can be Shortened by Activating Forced Shortened Deceleration Mode)
Dynamic Braking
Braking Start Frequency: 0 to Max Frequency; Braking Rate: 0 to 100%; Braking Time: 0 to 20 seconds
Input Terminal Functions
Forward/Reverse Run Input Signal, Jog Run Input Signal, Standby Signal, Preset-Speed Operation Input Signal, Reset Input Signal, etc.
Output Terminal Functions
Frequency Lower Limit Output Signal, Frequency Upper Limit Output Signal, Low-Speed Detection Output Signal, Specified Speed 
Attainment Output Signal, etc., Open Collector, RY Output
Failure Detection Signal
1 Form C Contact, Rated: 250 Vac, 2A, cosØ = 0.4
FM/AM Output
PWM Output: (1 mAdc Full-Scale DC Ammeter or 7.5 Vdc Full-Scale DC Ammeter/Rectifier-Type AC Voltmeter, 225% Current Max  
1 mAdc, 7.5 Vdc Full-Scale)
Protective Function
Stall Prevention, Current Limitation, Overcurrent, Output Short Circuit, Overvoltage, Overvoltage Limitation, Undervoltage, Ground Fault, 
Power Supply Phase Failure, Output Phase Failure Overload Protection by Electronic Thermal Function, Armature Overload at Startup, 
Load-Side Overtorque at Startup, Overheating Prevention, Detection of Analog Signal Break
Momentary Power Failure Protection
Auto-Restart Control after Momentary Power Failure
Electronic Thermal Characteristics
Switching between Standard Motor/Constant- Torque VF Motor, Overload Trip, Overload Stall Selection
4-Digit, 7-Segment LED
Frequency: Inverter Output Frequency
Alarm: Stall Alarm “C,” Overvoltage Alarm “P,” Overload Alarm “L,” Overheat Alarm “H.”
Status: Inverter Status (Frequency, Cause of Activation of Protective Function, Input / Output Voltage, Output Current, etc.) and Parameter 
Settings
Free-Unit Display: Arbitrary Unit (e.g. Rotating Speed) Corresponding to Output Frequency
Indicator
Lamps Indicate Inverter Status by Lighting, such as RUN Lamp and PROGRAM Lamp
Use Environments
Indoor-Altitude: 1000 Meters (Maximum), not Exposed to Direct Sunlight, Corrosive Gas, Explosive Gas or Vibration (Less than 5.9 m2)  
(10 to 55 Hz)
Ambient Temperature
-10 to +50˚C
Storage Temperature
-20 to +65˚C
Relative Humidity
20 to 93% Non-Condensing
 
TOSHIBA — Quality by Design
Toshiba's culture and history are strongly rooted in quality. Our designs are 
technologically innovative, and our products are manufactured from start to 
end using only the highest quality domestic and foreign parts. 
Product Warranty
Toshiba offers a comprehensive warranty program on its full line of industrial
products. Consult your salesperson or the factory for specific information.
Need to Know More?
Be sure to visit our website located at www.toshiba.com/ind for the latest
information on Toshiba products and services.
Customer Support Services
Toshiba offers 24-hour service nationwide. For assistance of any type 
call: 1-800-231-1412.
North America Headquarters & Manufacturing Facilities (Houston, TX)
Medium Voltage Motor
G7 Drive
ADJUSTABLE SPEED DRIVES    MOTORS    CONTROLS   UPS    INSTRUMENTATION     PLC
 
INDUSTRIAL DIVISION
13131 West Little York Road, Houston, Texas 77041
Tel 713/466-0277   Fax 713/466-8773
US 800/231-1412   Canada 800/872-2192   Mexico 01/800/527-1204
www.toshiba.com/ind
Copyright 8/2007  
Available Through:
*NC1brocct070815*