Installation and Quick Start
Expansion/Triple Chassis Installation
Overview
Use an Expansion Chassis or a Triple Expansion Chassis if the 
UPS has no card slot available.
The Management Card installs in the chassis and 
communicates with the 
UPS
 through the cable connection 
between the chassis and the 
UPS
.
When to use the 
AC
 adapter 
(AP9505)
Use the optional 
AC
 adapter with a chassis under the following 
circumstances:
• To connect the chassis to an independent 
AC
 input so 
that the Management Card can continue to operate if the 
UPS
 is turned off or fails.
• To provide the 
APC
 management products mounted in a 
Triple Expansion Chassis with more current than the 
UPS
 can provide through the 
UPS
-to-chassis cable.
– A Silcon UPS provides up to 500 mA.
– A Matrix-UPS, Smart-UPS, or Symmetra-UPS 
provide up to 200 mA.
For information about the current requirements for 
APC
 
management products, do the following:
a. Go to APC’s Support page (www.apc.com/support).
b. Click the Knowledge Base link in the “Search the 
Knowledge Base” section.
c. Use “current draw” as your search phrase.
d. Select the “Recommended connection order and 
power requirements for APC SmartSlot accessories” 
document.
Step 1: 
Disconnect the 
chassis from all 
power
Make sure that the chassis is disconnected from any power 
source: Disconnect the chassis cable from the 
UPS
 and, if the 
UPS uses an 
AC
 adapter, disconnect that adapter from the 
chassis.
Note
Use only a Silcon Triple Expansion Chassis 
(AP9604S) with a Silcon UPS.