Installation and Quick Start 
How to Recover from a Lost Password
You can use a local computer that connects to the Management 
Card or other device through the serial port to access the 
control console.
1. Select a serial port at the local computer, and disable any 
service that uses that port.
2. Connect the serial cable (940-0103) to the selected port 
on the computer and to the configuration port at the 
battery manager.
3. Run a terminal program (such as HyperTerminal
®
) and 
configure the selected port as follows:
– 9600 bps
– 8 data bits
– no parity
– 1  stop  bit
– no flow control.
4. Press 
E
NTER
, repeatedly if necessary, to display the User 
Name prompt. If you are unable to display the User 
Name
 prompt, verify the following:
– The serial port is not in use by another application.
– The terminal settings are correct as specified in step 3.
– The correct cable is being used as specified in step 2.
5. Press the Reset button. The Status LED will flash 
alternately orange and green. Press the Reset button a 
second time immediately while the LED is flashing to 
reset the user name and password to their defaults 
temporarily.
6. Press 
E
NTER
 as many times as necessary to redisplay the 
User Name prompt, then use the default, apc, for the 
user name and password. (If you take longer than 30 
seconds to log on after the User Name prompt is 
redisplayed, you must repeat step 5 and log on again.)
7. From the Control Console menu, select System, then 
User Manager
8. Select Administrator, and change the User Name and 
Password settings, both of which are now defined as 
apc.
9. Press 
C
TRL
-C
, log off, reconnect any serial cable you 
disconnected, and restart any service you disabled.