Troubleshooting
• 
Reset All Timers 
• 
Disable Outputs
• 
Enable Communications
• 
Present Sign-on Message to Diagnostic Terminal
7.2.4
 Performing a Hard Reset
A ‘Hard Reset’ clears the TankGate’s database.  The following procedure describes the 
steps necessary to perform a Hard Reset:
1. Set the ID DIP switch to 15 (all switches Closed/On).  This action initiates the Hard 
Reset Procedure.
Figure 7-1: Set the ID DIP switch to 15
2. Press the Reset button
Figure 7-2: Switches SW3 on the TankGate motherboard
3. The TankGate will perform its memory test.  When it has completed the memory 
test, all LEDs will be on.
ID = 15
EARTH
NEUTRAL
LINE
SURGE GND