Troubleshooting
TankGate Interface
100 
Installation and Operations Manual
4. Set the ID DIP Switch to the desired address (1-14).  At this point, there is no further 
action required by the user.
Figure 7-3: Set the ID DIP switch to the desired addresses
5. The LEDs will light (and remain steady) to indicate the address.  For example, if the 
ID DIP Switch is set to 1,  LEDS D1 will on.  If the ID DIP Switch is set to 3, LEDS D1 
and D2 will be on.
Figure 7-4: Address indication from the LEDs
6. After 10 seconds, the address of the TankGate will be set to the ID DIP Switch set-
ting.  The LEDS will flash for 5 seconds to indicate that the address is about to be 
set.
Figure 7-5: Set the ID addresses
7. After the address is set, the TankGate will begin normal operation with a blank 
database:
• 
CPU LED:  Flashing once per second
• 
COM LED:  Toggles when communicating to PC
• 
TXD: Off when there is no database.  When tank gauges are being scanned, the 
TXD LED will flash
• 
RXD: Off when there is no database.  When tank gauges are being scanned, the 
RXD LED will flash when a response is received.
ID = 1
ID = 1
D1
D2
D3
D4
ON
ID = 1
D1
D2
D3
D4
FLASHES