Using the Message Service
Section 6-3
SEND/RECV Flag Operations
• The Network Instruction Enabled Flag turns OFF during transmission or
reception, and ON after the data transmission or reception has been com-
pleted (regardless of whether an error occurs).
• The Network Instruction Error Flag retains its status until the next data
transmission or reception.
• Even when there is an abnormal end, the Network Instruction Error Flag
turns OFF when the next communications instruction is executed.
Example
Communications Instruction Response Codes
The status after a communications instruction has been executed is reflected
in the words shown in the following table. During instruction execution, it
becomes “00” or “0000,” and it is reflected here after the execution has been
completed.
Network Instruction Enabled Flag
Communications instruction
(SEND/RECV/CMND)
Network Instruction Error Flag
Communications instruction response code
Instruction 2
being executed
Instruction 3
being executed
Previous 
end
0
0
Instruction 1
being executed
00
00
00
00
04
00
(Normal 
end)
(Normal 
end)
(Busy)
PLC
Word
Bits
Contents
CS/CJ-series
A203
---
Port 0 response code
A204
---
Port 1 response code
A205
---
Port 2 response code
A206
---
Port 3 response code
A207
---
Port 4 response code
A208
---
Port 5 response code
A209
---
Port 6 response code
A210
---
Port 7 response code
C200HX/HG/HE
SR 237
08 to 15
Operating level 1 response code
00 to 07
Operating level 0 response code
CVM1 and CV-
series
A503
---
Port 0 response code
A504
---
Port 1 response code
A505
---
Port 2 response code
A506
---
Port 3 response code
A507
---
Port 4 response code
A508
---
Port 5 response code
A509
---
Port 6 response code
A510
---
Port 7 response code
CQM1H-series
AR 02
00 to 07
Response code